PERFORMANCE DATA — 542J (cont)

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 542J150,180

LEGEND

*Units with electric heat are not designed to operate at these ranges.
NOTES:

1. Heaters are rated at 208/240 v, 480 v, and 600 v.

2. The static pressure must be added to external static pressure. The

sum and the indoor-air section entering-air cfm should then be
used in conjunction with the Fan Performance table to determine
blower rpm, bhp, and watts.

ELECTRIC HEATING CAPACITIES — 542J150,180

*Maximum number of stages using accessory outdoor-air thermostats.

NOTE: Heaters are rated at 208 v, 240 v, 480 v, and 600 v. See multipli-
cation factors table on page 152.

ACCESSORY/FIOP

UNIT SIZE

UNIT VOLTAGE

kW

CFM

3750

4500

5000

5600

6000

6250

7200

7500

Electric Heaters

150

208/230-3-60

14-34

0.05

0.05

0.07

0.08

0.09

0.09

0.11

0.12

42,56

0.06

0.06

0.08

0.10

0.12

0.13

0.16

0.17

460-3-60

15,32

0.05

0.05

0.07

0.08

0.09

0.09

0.11

0.12

55

0.06

0.06

0.08

0.10

0.12

0.13

0.15

0.15

575-3-60

37

0.06

0.06

0.08

0.10

0.12

0.13

0.15

0.17

180

208/230-3-60

26,34

*

*

*

0.08

0.09

0.09

0.11

0.12

42,59

0.10

0.12

0.13

0.16

0.17

460-3-60

32,55

*

*

*

0.08

0.09

0.09

0.11

0.12

0.10

0.12

0.13

0.15

0.17

575-3-60

50

*

*

*

0.13

0.15

0.16

0.20

0.21

EconoMi$erIV and

EconoMi$er2

150,180

All

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.10

Glycol Coil

150,180

All

0.16

0.18

0.25

0.31

0.35

0.37

0.44

0.46

FIOP — Factory-Installed Option

UNIT 542J

HEATER kW

HEATER
STAGES

% HEAT

PER STAGE

MAXIMUM

STAGES*

Unit Voltages

208

230

460

575

150

14

19

15

1

100

1

26

34

32

2

50/50

2

42

56

55

37

2

33/67

3

180

26

34

32

2

50/50

2

42

56

55

2

33/67

3

50

2

50/50

4

5

42J