♦ Fourth Press

If a Wire Length has been entered, displays

the minimum Wire Ampacity rating. If no Wire

Length has been entered, displays the NEC

table referenced for the calculation.

 

125% ampacity — Used for Motor Wire Sizing

when the Wire must not exceed 80% of its rated

Ampacity (125%A). This keystroke calculates Wire

Size based on 125% of the entered or calculated

Amps value.

parallel Size — Used to find the size of parallel

conductors using Amperage and an entered

quantity of Wires. Parallel Wire Size calculations

smaller than 1/0 will display

none, as the NEC

does not allow Parallel Wire runs smaller than 1/0.

♦ First Press

When preceded by a number, calculates the

applicable Wire Size for that quantity of

Wires in parallel.

♦ Second Press

Displays the maximum adjusted Ampacity of the

calculated Parallel Wire Size.

Note: No adjustments are made for deration.

 

Derated Wire Size (D/r Size) — Used to

calculate Derated Wire Sizes and allowable

Ampacity based on the entered quantity of wires,

NEC Table 310.15(B)(16) and NEC Table

310.15(B)(3)(a). Derated Wire Sizes are not

calculated when there are less than four Wires, or

when the unit is in Free Air mode.