12 — e

lectri

c

alc

®

P

ro

(cont’d)

 

Wire resistance (Wire res) — Displays the

actual Resistance per 1,000 Feet of the Wire Size

in  based on NEC Chapter 9, Table 8.

Grounding Conductor Keys

Ground — Used to find the Grounding electrode

conductor size for AC systems based on NEC

Table 250.66 and an entered or calculated

service-entrance conductor (largest size). Only

actual Wire Sizes are considered valid entries.

♦ First Press

Calculates the copper Grounding electrode

conductor size if you have entered a valid

Wire Size.

♦ Second Press

Displays the aluminum Grounding electrode

conductor size.

♦ Third Press

Displays the Circular Mil area used to calculate

the Grounding electrode conductor size.

♦ Fourth Press

Displays the NEC table referenced for

the calculation.

 

equipment Ground (eqGrnd) — This function

uses NEC Table 250.122 to calculate the

minimum equipment Grounding conductor size,

given an entered Amperage rating or setting for

an over-current device up line.

Note: This function deviates from the NEC Table

250.122 in that 1250 MCM AL is used instead of

1200 as specified in NEC Table 250.122.

♦ First Press

Displays the copper Grounding conductor size

for the entered Amp rating.

Advertising