Calculated Industries 5070-B User Guide User Manual

Page 43

Advertising
background image

42 — e

lectri

c

alc

®

P

ro

2 Set to 60º C:

 

(60º)

3Ø 60

3 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

60 Cu

3 Ph

4. Enter Amps:

  

aMPs 15.

5. Enter Volts:

   

VolT 240.

6. Enter Wire Size:

  

*

aWG 10 Cu

WIRe sIZe

7. Enter 3% allowable Voltage Drop:

 

DRoP 3.0

% V

8. Find distance:

feeT 234.86987

9. Find actual Voltage Drop:

DRoP 7.2

V

10. Find percent Voltage Drop:

DRoP 3.0

% V

* Wire size can also be entered in Circular Mils (e.g.,

     

enters 10,380 CMILs and displays 10 AWG

Wire Size).

Note: The calculator automatically makes adjustments for Resistance

using NEC Chapter 9, Table 8, if the Insulation Type is other than 75°C.

(cont’d)