• To reduce power consumption and extend battery life, slower sample and reporting rates are used. Faster sample and report rates

can be configured, but this will decrease the battery’s life. For details, refer to the included table of DIP switch configurable parame-
ters.

• The FlexPower switched power management system can operate a FlexPower Node and a sensing device for up to five years on a

single lithium D cell.

Warmup Time

0 Volts

Switch Power

Sample point

Sample point

Sample interval

Voltage

Storage Mode and Sleep Mode

While in storage mode, the radio does not operate. All SureCross® radios powered from an integrated battery ship from the factory in
storage mode to conserve the battery. To wake the device, press and hold button 1 for five seconds. To put any FlexPower® or integra-
ted battery SureCross radio into storage mode, press and hold button 1 for five seconds. The radio is in storage mode when the LEDs
stop blinking, but in some models, the LCD remains on for an additional minute after the radio enters storage mode. After a device has
entered storage mode, you must wait one minute before waking it.
During normal operation, the SureCross radio devices enter sleep mode after 15 minutes of operation. The radio continues to function,
but the LCD goes blank. To wake the device, press any button.

LED Behavior for the Nodes

After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.

LED 1

LED 2

Node Status

(flashing green)

Radio Link Ok

(flashing red)

(flashing red)

Device Error

(flashing red, 1 per 3 sec)

No Radio Link

Modbus Register Table (Analog or Discrete Configuration)

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register Repre-
sentation

Terminal

Block La-

bels

Gate-

way

Any Node

Min.

Max.

Min. (Dec.)

Max. (Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

-

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

-

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Analog IN 1+

mA / V

0.0

20.0 / 10.0

0

65535

A1+

4

4

4 + (Node# × 16)

Analog IN 2+

mA / V

0.0

20.0 / 10.0

0

65535

A2+

...

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Discrete OUT 1

-

0

1

0

1

DO1

SureCross DX80 FlexPower Node

P/N 131296 Rev. L

www.bannerengineering.com - tel: 763-544-3164

7

Advertising