Modbus Register Table

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register
Representation

Terminal

Block La-

bels

Gateway

Any Node

Min. Val-
ue

Max.
Value

Min.
(Dec.)

Max.
(Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

-

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

-

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Analog IN 1

mA

0.0

20.0

0

65535

A1

4

4

4 + (Node# × 16)

Analog IN 2

mA

0.0

20.0

0

65535

A2

5

5

5 + (Node# × 16)

Battery Sense (inter-
nal)

V

0.0

10

0

65535

A3

6

6

6 + (Node# × 16)

Thermistor IN

°F/°C

-1638.3

+1638.4

-32768

32767

A4

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

10

10

10 + (Node# × 16)

Discrete OUT 2

-

0

1

0

1

DO2

11

11

11 + (Node# × 16)

12

12

12 + (Node# × 16)

13

13

13 + (Node# × 16)

14

14

14 + (Node# × 16)

Switch Power (inter-
nal)

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Node Modbus Register: The Gateway uses the first 16 registers followed by each Node in the network, based on the Node address. For
Node 5, the starting Modbus registers are 1 + (Node# Ч 16) = 1 + (5 Ч 16) = 81, the ending register is 97.
Use one of Omega’s 44006 or 44031 families of 10kΩ thermistors.
The Battery Sense feature detects if the Node is being powered by the solar assembly, 10-30V dc, or by the DX81P6 6-Pack Battery
Supply Module. The sensor reads 5.0V for solar power, 4.0V for 10-30V dc power, and 3.6V when powered by the DX81P6.

SureCross DX80 FlexPower Solar Node

P/N 140373 rev. B