Device Configuration

DIP Switch Changes

Before making any changes to the DIP switch positions, disconnect
the power. For devices with batteries integrated into the housing,
remove the battery for at least one minute.
DIP switch changes will not be recognized if power isn't cycled to
the device.

Accessing the DIP Switches

To access the DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For Class I, Division 2 certified devices, skip this

step (the ribbon cable is glued).

4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials. After making the neces-
sary changes to the DIP switches, place the black cover plate back into posi-
tion and gently push into place. Plug the ribbon cable in after verifying that
the blocked hole lines up with the missing pin. Mount the cover back onto the
housing.

DIP Switch Settings

Switches

Device Settings

1

2

3

4

5

6

7

8

Rotary dial address mode

OFF*

Extended address mode

ON

Host configured (overrides switches 3-8)

OFF*

Use switch settings

ON

Inputs Sinking (NPN)

OFF*

Inputs Sourcing (PNP)

ON

Boost Voltage: 6 Volts

OFF*

OFF*

OFF*

Boost Voltage: 13 Volts

OFF

OFF

ON

Boost Voltage: 17 Volts

OFF

ON

OFF

Boost Voltage: 21 Volts

OFF

ON

ON

Boost Voltage: Battery In

ON

OFF

OFF

Boost Voltage: User configuration

ON

OFF

ON

Boost Voltage: User configuration

ON

ON

OFF

SureCross DX80 FlexPower Solar Node

6

www.bannerengineering.com - tel: 763-544-3164

P/N 140373 rev. B