The modern design and attractive appearance of the models
BW4 and BW5 Oil-Fired Water Boilers make them ideal for
installation in any area. The boilers are shipped fully
assembled and wired, including all controls (except barometric
draft regulator). The compact 22-gage steel cabinet has a
baked-on enamel paint finish for durability. A 1-in. layer of
thermal insulation is applied inside the jacket for protection
and thermal efficiency. The flame retention head burner

provides efficient fuel usage. A wet base cast iron block with thermal
pins surrounds the combustion area for better heat transfer from flue
gases to water.

FEATURES

BAROMETRIC DRAFT CONTROL

—The factory supplied

barometric draft control can easily be installed in the vent pipe for
optimum draft and combustion efficiency.

CONTROLS

—Factory-wired controls on units with tankless hot

water coil include a triple aquastat relay with high/low limit
protection and circulator control.

COMBINATION TRANSFORMER AQUASTAT

—A 24-v

transformer is combined with the aquastat assembly. The
transformer will supply power efficient to power a 3-zone system
on BW5 models. Factory installed combination pressure/
temperature gage and a pressure relief valve.

COIL OPTIONS

—Units are available with or without tankless

heater coil. The coil provides a supply of hot water for normal
domestic purposes or an accessory tankless heater coil can be
added later.

FACTORY INSTALLED FEATURES

—A factory-installed drain is

provided should the boiler ever need to be drained. Oil primary
control prevents boiler in operation in the event of flame loss.

SECTIONS TESTED

—Each section is hydrostatically tested to 50

psig. Individual sections are tested to 125 psig at factory.
Assembled sections are tested to 75 psig at the factory. The
maximum allowable pressure is 50 psig for hot water boilers.

EASE OF INSTALLATION

—Circulator is shipped pre-wired

with 6 ft bx conduit for easy installation for supply side pumping.

WARRANTY

—The cast-iron sections are covered by a non-

prorated 20-year warranty on the entire assembly. Oil burner and
circulator pump covered by 3-year warranty. All other parts are
covered by a 1-year limited warranty.

SOLENOID OIL VALVE

—This provides cleaner burning and

quieter operation. Valve is included on all burner types.

SWING BURNER DOOR

—This unique design offers uninhibited

access for set-ups, service, and maintaining the burner. Routine
cleaning is also much easier.

MODELS BW4 and BW5

SPECIFICATIONS

UNIT SIZE

120

181

239

GENERAL DATA

Sections — Fine Grain Cast Iron

No.

3

4

5

Water Capacity

Gal

9.6

11.6

13.7

Combustion Chamber Target Wall

Ceramic Fiber

Draft Regulator

Furnished

OIL BURNER

Type Manufacturer/Model

Beckett/Model AFG Flame Retention Head Burner

Oil Pump

Single Stage

Fuel Type

No. 1 or 2 Fuel Oil

Rated Load Amps

3 Amps

CONTROLS

Combination Control

Without Heater

High Limit, Circulator Relay, & Cad. Cell Relay

With Heater

High & Low Limit, Circulator Relay, & Cad. Cell Relay

Pressure/Temperature Gage

Psig

0–60

°

F

60–260

ASME Pressure Relief Valve

Psig

30

CIRCULATOR

Taco

Model

007

Full Load Amps

0.70

Flange Size FPT

In.

1-1/4