PC15CP PUMP CONTROLLER OPERATION / MAINTENANCE MANUAL

PAGE 5

2

PC15CP CONTROLLER OPERATION

The controller is operated by using the buttons located on the PLC, see Table 2-1.

Table 2-1: PLC Buttons

Button

Action from “Home Page”

Action from “Menu Pages”

Scroll through Menu pages

Go to Home page

Enables/Disables controller
cycling

Navigate between Menu pages

Increases pump cycle rate on
Home page

Increase values

Decreases pump cycle rate on
Home page

Decrease values

2.1 TURNING PUMP ON AND OFF

From the Home Page, pressing the RIGHT arrow key () will start and stop the
cycling of the pump controller. When cycling, a cursor will oscillate under positions
“1” & “2”.

Figure 3: Controller Cycling

2.2 ADJUSTING CONTROLLER

2.2.a Suggested Controller Values

Flow Rate

CPM

Air Flow Control

Overlap

- 0-4 LPM:

“000030”

“3” Turns from closed

20

- 3-6 LPM:

“000056”

“2” Turns from closed

10

Please contact Trebor Service Group for any updates on these settings.