PC15CP PUMP CONTROLLER OPERATION / MAINTENANCE MANUAL

PAGE 9

3

REMOTE OPERATION

To operate the controller by a remote signal, the following conditions must be met:

Input 1 (I1) must have a source input sufficient (>9 VDC) to activate the input as

indicated in the display below to activate the remote operation capabilities.

Input 2 (I2) must have a switched source input sufficient (>9 VDC) to activate the

input in conjunction with I1 to turn the controller ON (High Signal) or OFF (Low
Signal) as shown in the display below.

Figure 8: Remote Mode (ON)

Figure 9: Remote Mode (OFF)

During remote operation, the controller can be manually stopped by pressing the RIGHT
arrow key () from the HOME page, this will locally stop controller oscillation. While in the
override stop state, the cursor under the position 8 will be ON (Figure 8).

To resume pump operation toggle input I2 changing its state (ON state to the OFF state)
resetting output 8 and then turning I2 on again. In order to turn the controller on locally exit
out of remote mode (I1 = OFF) then from the Home Page, press the RIGHT arrow key ()
will start and stop the control of the pump as normal.

Figure 10: Local Override Stop Display

Pump status feedback is provided on output Q3. As indicated in Figure 8 and 9 this output
may be wired to provide an indication signal of pump operation