DESCRIPTION

Two basic types of Ruffneck™ Heat Exchanger configurations are available from CCI Thermal Technologies Inc.:

FR (Frost Resistant) Series - for steam service only, up to 100 psi (690 kPa) on select models

HP (High Pressure) Series - for steam and liquid service up to 400 psi (2,700 kPa) on select models

LOCATION OF HEATERS

The following guidelines have been established by CCI Thermal Technologies Inc. to ensure that you properly locate the

heaters in your building. These are only suggestions, and variations may be deemed necessary depending on application.

1. When occupant comfort is the major objective, heaters should be positioned so that the airflow is directed to areas

of highest heat loss (i.e., doorways, windows and outside walls).

2. For personnel comfort, a less turbulent and more even air distribution is required. To achieve this effect a larger

quantity of smaller unit heaters should be installed.

3. When equipment protection is of utmost concern, heaters should be positioned so that the airflow is directed

towards the equipment.

4. In very large areas, arrangement of heaters should be such that the air will exit from one heater and be projected

towards the inlet, or back, of another heater. A rotational airflow will result, with air circulation in the central area of

the building.

INSTALLATION

IMPORTANT NOTICES

WARNING!

Read and adhere to the following. Failure to do so may result in severe or fatal injury.

WARRANTY WILL BE VOID

IF INSTRUCTIONS ARE NOT FOLLOWED

1. Read and follow the instructions in this manual.

2. Heater to be used only in the hazardous locations indicated on the

heater’s data plate.

3. Heater is for dry indoor use only. Do not immerse in water. Do not

store or use in areas exposed to rain or snow.

4. Heater is to be connected and serviced only by a qualified electrician

experienced with hazardous location equipment.

5. Installation, piping, and wiring of he heater must adhere to all

applicable codes.

6. It is essential that any unit heater that will be used in a hazardous

(classified) location is equipped with a electric motor approved for

such service, and the temperature of the heat transfer medium is

below the ignition temperature of the atmosphere. Refer to applicable

electrical codes for additional information.

7. Disconnect heater from power supply at integral disconnect or fuse

box before opening enclosures or servicing heater. Lock the switch in

the “OFF” (open) position and/or tag the switch to prevent unexpected

power application. IF INTEGRAL DISCONNECT IS BEING

SERVICED, verify that power has been disconnected at fuse box or

main panel. Lock the switch in the “OFF” (open) position and/or tag

the switch to prevent unexpected power application.

8. Do not operate heater in atmospheres which are corrosive to steel

or aluminum, unless it has been coated with a factory approved

protective coating.

9. For steam service use only single-pass models. Refer to model

coding (page 7) for number of passes in heat exchanger.

10. Refer to heat exchanger data plate for pressure and temperature

limits.

11. Heater must be kept clean. When operating in a dirty environment,

regularly clean the finned tubes, fan and fan guard. Follow the

recommended maintenance procedures. Refer to the “Heater

Maintenance Checklist” section for details.

12. Use factory approved replacement parts only.

13. If there are any questions or concerns regarding the heater, contact

the factory. Refer to the last page of this manual for details.

14. HVAC fluids must be non-flammable, non-compressable, non-

explosive & non-toxic.

15. Do not operate the heater with any of the louvers fully closed or

overriding their stops.

16. Do not operate heater in ambient temperatures above 104°F (40°C).

17. See applicable electrical codes for seal requirements in field installed

conduits. Factory installed conduits require no further sealing.

18. Base of the heater is to be mounted a minimum of 7.9 ft (2.4 m)

above the floor. Refer to the “Installation” section for details.