FIG.2

UNIT HEATER CONNECTION

FOR LOW-PRESSURE STEAM,

OPEN GRAVITY OR VACUUM

RETURN SYSTEM

NOTES:

1. For medium to high-pressure systems a bucket
or float trap must be used.
2. Do not use with fluids corrosive to steel.
3. Install using proper piping practices
4. In horizontal pipe runs, use eccentric reducers only.
5. Use a properly sized steam trap.

FIG.3

UNIT HEATER CONNECTIONS

TO OVERHEAD STEAM AND

RETURN MAINS

NOTES:

1. This piping arrangement is only for two-position-type
control. Modulating steam control may not provide
sufficient pressure to lift condensate to return main.
2. Do not use with fluids corrosive to steel.
3. Install using proper piping practices.
4. In horizontal pipe runs use eccentric reducers only.
5. Use a properly sized steam trap.

TAP INTO TOP OF MAIN

SHUT-OFF VALVE

UNION

PITCH DOWN

UNION

RETURN

MAIN

TAP INTO TOP OF MAIN

SHUT-OFF VALVE

PITCH DOWN

FULL SIZE DROP LEG

10.0 in. Min.

(254 mm)

SHUT-OFF VALVE

RETURN MAIN

PITCH

DOWN

LIFT NOT TO EXCEED 1 FT FOR

EACH POIND PRESSURE

DIFFERENCE BETWEEN STEAM

AND RETURN MAINS

THERMOSTATIC AIR

VENT OR PETCOCK.

(INSTALL IF TRAP DOES

NOT HAVE AIR VENT)

SHUT-OFF

VALVE

FLOAT AND

THERMOSTATIC

TRAP

STEAM

MAIN

UNION

UNION

UNION

UNION

SWING CHECK VALVE

STEAM TRAP WITH AIR VENT

STAINER AND DRAIN VALVE

6 in. (152mm) LONG

FULL SIZE

DIRT POCKET

STAINER

10 IN. Min.

(254 mm)

FULL SIZE DROP LEG

6 in. (152mm) LONG

FULL SIZE

DIRT POCKET

UNION