5. When arranging heaters, check the fan throws for the heaters being mounted (see table below). Although it is not

generally required that the fan throws reach the next heater, air circulation must be sufficient to prevent cold spots

from occurring.

6. Do not install heaters such that airflow is blocked or impeded by equipment or walls.

7. For warehouses or large workshops, it may be acceptable to use fewer, but larger, heaters mounted well above floor

level. It has to be recognized, however, that only the largest heaters have long fan throw distanced.

FAN THROWS FOR RUFFNECK

TM

HEAT-EXCHANGER UNIT AIR HEATERS

MODEL

FR/HP - 12

FR/HP - 16

FR/HP - 20

FR/HP - 24

FR/HP - 30

FR/HP - 36

MOTOR HP

1/2

1/2

1/2

1/2

3/4

1 1/2

RPM
1725

1725

1725

1725

1140

1725

THROW IN FEET

40

60

65

70

70

60

NOISE LEVELS

Where personnel inhabit a room or building for long periods of time, and local ambient noise levels are low, the noise from

the heaters has to be considered. Typically, the smaller the heater the lower the noise level will be. The largest heaters

that move large volumes of air are noticeably noisier than units handling low volumes of air.

MEASURED SOUND LEVELS OF RUFFNECK

TM

HEAT-EXCHANGER AIR UNIT HEATERS

MODEL

FR/HP - 12

FR/HP - 16

FR/HP - 20

FR/HP - 24

FR/HP - 30

FR/HP - 36

REAR

61

70

66

74

74

76

FRONT

61

70

66

74

74

76

SOUND LEVEL dBA

Note:

Sound levels were measured at a distance of 15 feet with louver blades horizontal and sound

meters on centre line of heater (i.e., in line with motor/fan shaft).

MOUNTING

Although Ruffneck™ Unit Heaters are designed to be installed in an upright and level position, they may be installed

in other positions. However, for steam service the inlet must be above the outlet and the bottom of the core must drain

toward the outlet. They are designed to be suspended from the top of the cabinet either with two or four (depending on

model) 5/8” NC bolts screwed into internally threaded holes provided in the cabinet top panel. It is essential that adequate

structural support be provided for installation.

Basic Mounting Kits (BMK), Hanging Mounting Kits (HMK), Swivel Hanging Mounting Kits (SHMK) or Wall Mounting Kits

(WMK) are available for Ruffneck™ heaters. If the strength of the structure is not adequate to support the units, a suitable

alternative such as the Ruffneck™ Pipe Mounting Kit (PMK) would be recommended to ensure safe and proper operation.

The HMK is the only suitable mounting kit for the 30” and 36” heater models.