Fan maintenance checklist, Warning – CCI Thermal Technologies EFX - Explosion-Proof Exhaust Fan User Manual

Page 2

Advertising
background image

- 2 -

For assistance, please call

Toll Free: 1-800-661-8529 (24 hrs)

U.S. & Canada

FAN MAINTENANCE CHECKLIST

For Explosion-Proof Exhaust Fan

PERIODIC (before and as required during heating season)

Remove dust using compressed air. Do not spray with water or solvents.

ANNUAL (before heating season)

WARNING

Fan should only be serviced by qualified personnel with HVAC equipment experience.

Disconnect fan from power supply before servicing fan. Lock the switch in the “OFF”

(open) position and/or tag the switch to prevent unexpected power application.

1.

CLEAN

Fan

Fan Guard

Motor

Backdraft Dampers

Stormhood

2.

CHECK

Motor for smooth, quiet operation

Dampers for proper angle and tightness

1. ELECTRICAL

Check all terminal connections and conductors. Tighten loose connections. Conductors with damaged

insulation must be replaced.

2. MECHANICAL

Check motor shaft bearing play. Replace motor if play is excessive or motor does not run quietly and

smoothly. Motor bearings are permanently lubricated.

Check fan. Replace immediately if cracked or damaged.

Check the tightness of all hardware. All nuts and bolts, including mounting hardware, must be tight.

TURN FAN ON FOR A MINIMUM OF 15 MINUTES. Check for air exiting fan through dampers and

smooth running of fan motor.

Heaters for the Harshest Environments