FIGURE 2

- 4 -

MOUNTING CLEARANCES

1. Leave at least 20” (500mm) clearance between

the rear of the motor and the nearest obstruction.

2. Clearance equal to the height of the fan shroud

above, or beneath is required for easy fan or

motor replacement.

TEMPERATURE CONTROL

1. If required, the fan output may be thermostatically

controlled by a remotely mounted thermostat.

FINAL INSPECTION

1. Before application of electrical power:

a. Check that all connections are secured and

comply with the applicable wiring diagram

and code requirements

b. Confirm the power supply is compatible with

the data plate rotating on motor.

c. Remove any foreign objects from fan.

d. Ensure all electrical covers are well secured.

e. Ensure the fan rotates freely

counterclockwise when viewed from the rear

of the fan and air exits through the dampers.

B

F

G

A

E

AIR FLOW

C

D

C

D

C

D

C

D

EFX-12

EFX-16

EFX-20

EFX-24

EFX-30

mm

392.1

377.8

409.6

393.7

396.9

in

15.4

14.9

16.1

15.5

15.6

mm

461.9

588

687.9

787.9

942.3

in

18.2

23.2

27.1

31

37.1

mm

410

512.5

614.5

714.5

862.5

in

16.1

20.2

24.2

28.1

34

mm

79.4

57.2

91.7

76.2

88.9

in

3.1

2.2

3.6

3

3.5

mm

373.3

475.6

577.3

677.3

835.3

*

in

14.7

18.7

22.7

24.7

32.9

mm

411.1

537.2

637.1

737.1

891.5

in

16.2

21.2

25.1

29

35.1

mm

359.2

461.7

563.7

663.7

811.7

in

14.1

18.2

22.2

26.1

32

* This dimension is the minimum square opening size

E

F

G

DIMENSION

A

B

C

D

Advertising