Exide Technologies GB4128 User Manual

Page 12

Advertising
background image

Ferro Magnetics Corporation, St. Louis, MO

2.1.9. F3 (LOW BATTERY) OVERRIDE

If battery volt age is below 1.6 volt s per cell the charger will not start automatically. If this i s due to an

overly discha rged battery of the corre ct volt age, t he F3 fault can be manu ally overrid den by pre ssing

POWER ON while the F3 Fault message (Low Battery) displays.


2.1.10. DISPLAYING ADDITIONAL CHARGE INFORMATION

The user can view many different parameters associated with a charge. By pressing an appropriate key,

information such as charger run time or amp-hours returned can be viewed. The display will time out after

about 7 seconds and return to the default display which is usually amps.


2.1.10.1. DISPLAY SOFTWARE VERSION

To display the sof tware version number press ‘ 5’. The display will show ‘ UEr’ followed by the sof tware

version number (e.g. 4.00). Note: The letter V is displayed as ’U’.


2.1.10.2. DISPLAY CHARGING CURRENT

In most a pplications charging current is no rmally displayed. If chargi ng current is not al ready bei ng

displayed, p ress ‘ D.C. AMPS’ to view . The DATA di splay sh ows cha rging cu rrent in am ps. The UNITS

display shows ‘A ‘ for amperes.


2.1.10.3. DISPLAY VOLTS PER CELL

To view the a verage volts per cell, press ‘VOLTS CELL’. The DATA display shows the volts per cell and

the UNITS d isplay sh ows ‘VC’ fo r vol ts p er cell. If the charge ha s fini shed an d the b attery is stil l

connected, the en d volt s per cell is displayed. Repeatedly pressing th e ‘ VOLT CELL’ key will toggl e

between volts per cell and full battery voltage.


2.1.10.4. DISPLAY FULL BATTERY VOLTAGE

To view battery volt age, press ‘VOLTS CELL’ twice. The DATA display shows the full battery volt age and

the UNITS display shows ‘V’ for volts. If the charge has finished, the end full battery voltage is displayed.

Repeatedly pressing the ‘VOLT CELL’ key will toggle between volts per cell and full battery voltage.


2.1.10.5. DISPLAY AMP-HOURS

To view amp-hours returned to the batte ry, press ‘AH’S RT’ND’. The DATA display shows the amp-hours

returned to the battery so far during the current charge. The UNITS display shows ‘AH’.


2.1.10.6. DISPLAY TOTAL CHARGER AMP-HOURS (V4.02 OR HIGHER)

To view the tot al accumulated amp-hours supplied by the charger, press ‘AH’S RT’ND’ twice. The DATA

display shows the total amp-hours accumulated by the charger since the control was installed in 2 steps.

The u pper 4 digit s a re displayed with the ri ght d ecimal point li t, followed b y the lo wer 4 digit s. F or

example, a display of ‘ 1234.’ follo wed by ‘ 5678’ would in dicate a to tal amp-hours accumulated of

12,345,678 Ah. The UNITS display shows ‘AH’.


2.1.10.7. DISPLAY TIME-OF-DAY START TIME

To view the t ime-of-day start time, press ‘ST ART TIME’. The DATA display shows the time -of-day start

time in hours and minutes, and the UNITS display shows ‘HM’ for hours and minutes format. The time-of-

day is in 24-hour format. Thus a start time of 4:30PM would be displ ayed as ‘ 16.30’. If the time-of -day

start is not active, the display shows ’99.99’.


2.1.10.8. DISPLAY CHARGER RUN TIME

To view ch arger run time so far, press ‘RUN TIME’. The DATA display shows the run time i n hours and

minutes and the UNITS display shows ‘HM’ for hours and minutes format.


2.1.10.9. DISPLAY CHARGER IDENTIFICATION NUMBER

Chargers that are part of the TOBi® Battery Management System have a unique identifying number. To

view this ‘ID’ number, press ‘CHGR. ID’. The DATA display shows the charger ID number. If no number is

set, the DATA display shows ‘9999’. UNITS display is blank.