Exide Technologies GB4128 User Manual

Page 6

Advertising
background image

Ferro Magnetics Corporation, St. Louis, MO

1.4. AC SERVICE REQUIREMENTS

Follow local code requirements if they are different than the in structions in this manual. After ch ecking

the transformer connections as d escribed in Parag raph 1.3, refer to Table 1-1, to determine the corre ct

ratings for the AC cable, AC fuses, and AC service disconnect switch for the line amperes as listed on the

nameplate of the charger for the available AC voltage

TABLE 1-1

Line Amperes Disconnect

Switch

Fuse Size Amps

000.0 - 02.5

30A

05

003.0 - 04.5

30A

07

005.0 - 07.5

30A

10

008.0 - 11.0

30A

15

011.5 - 15.5

30A

20

016.0 - 18.0

30A

25

018.5 - 22.0

30A

30

022.5 - 27.0

60A

35

027.5 - 32.0

60A

40

032.5 - 40.0

60A

50

040.5 - 48.0

60A

60

048.5 - 64.0

80A

80

065.0 - 80.0

100A

100

081.0 - 95.0

125A

125

096.0 - 125.0

150A

150

For voltages up to 240, use a 240 volt disconnect switch.

For voltages greater than 240 to 600, use a 600 volt disconnect switch.

Two conductors and ground wire required for single phase.

Three conductors and ground wire required for three-phase


1.5. CONNECTING AC SERVICE TO THE CHARGER
1.5.1. SINGLE-PHASE MODELS

Connect the AC service to the L1 and L2 terminals located at the end of the AC fuse block.


Note:

If the charger has been ordered with an AC input door-mounted disconnect switch, the AC input

wires will be connected to the L1 and L3 terminals at the top of the switch body.

1.5.2. THREE-PHASE MODELS

Connect the AC service to the L1, L2 and L3 terminals located at the end of the AC fuse block.


Note:

If the charger has been ordered with an AC input door-mounted disconnect switch, the AC input

wires will be connected to the L1, L2 and L3 terminals at the top of the switch body.

1.6. GROUNDING THE CHARGER

The charger must be grounded to the AC system ground for personnel safety.

The green ground wire in the AC input wiring must be connected to the charger ground stud

(Identified by a green dot and ground symbol).

1.7. BATTERY CONNECTOR AND CHARGING CABLE

Verify that the connectors on both the battery and the charger are attached so that the positive output

terminal of the charger is connected to the positive battery terminal.

CAUTION:

If the polarity is reversed, the DC fuse will blow. If in doubt, check the polarity with a

DC voltmeter.

1.8. CHARGING RATE ADJUSTMENT

The charging rate has been set at the factory; therefore, field adjustment should not be necessary.

Consult factory.