Exide Technologies GB4128 User Manual

Page 7

Advertising
background image

Ferro Magnetics Corporation, St. Louis, MO

2. OPERATION

2.1. 046-0172 CONTROL

The charger utilizes a

controlled ferro-r esonant transformer , whi ch prov ides

isolation fro m the AC service lin e and regulates the charging current. The

transformer output is connected to a full- wave bridge of silicon diod es, which

provides DC charging current to the battery.
The starting charge amps and length of time required for a charge vary depending

on the charger m odel, a nd si ze of batt ery. See th e data plate o n the cha rger for

specific information.


2.1.1. FEATURE SUMMARY

Automatic start when the battery is connected, or manual start (if selected).

Automatic stop when charge is finished.

Fully charges partially discharged batteries without overcharging.

Dead battery ‘jump start’ for overly-discharged batteries.

Equalize charge by user request.

Automatic shut-down if battery starts to overheat.

Automatically resumes charge after a power failure during the charge cycle.

Displays charging amps, battery volts/cell, full battery voltage, amp-hours returned, and run time.

Delayed start adjustable from 1 minute to 24 hours.

Delayed start until a certain time-of-day.

Automatic equalize by number of charges.

Automatic equalize by day-of-week.

Charge indication codes with descriptive messages.

Cool down timer adjustable from 1 minute to 24 hours.

Periodic alert messages describing charger status.

Compatible with the Tobi® Battery Management System.

TOBi® is a registered trademark of Ferro Magnetics Corporation, St. Louis, Missouri

CAUTION: If the battery must be disconnected before the end of the charge cycle, the charger
must be turned off first. Press the ‘ON/OFF’ key. The MODE portion of the display will show ‘OF’
for OFF and the DATA portion of the display will show ‘OFF ’. The battery may then be safely
disconnected.