Radiance Direct Vent/Natural Vent Gas Heater

20004188

Thermostat Connection (optional)

Use only a thermostat rated for 500 - 750 millivolts.

Check the table below for the appropriate gauge ther-
mostat wire to use for the length of lead required in your
installation.

1. Install the wall thermostat in the desired location and

run the wires to the stove location. Terminate these
leads with 1/4” female connectors.

2. Connect the thermostat wires to the valve. (Fig. 43)

Install ON/OFF Switch

The switch assembly parts are found in the parts bag.
1. Attach switch assembly to left rear side of stove

shroud (when facing shroud) using two screws and
existing holes in shroud. (Fig. 42)

2. Run wires down back of stove, under bottom of rear

shroud to valve.

3. Attach wires to valve terminals. (Fig. 43)

PILOT

ADJ

TP

TH

TPTH

ST228

attach switch

wires to valve

12/99

ST228

Fig. 43 Attach switch wires to valve.

Install the Mesh and Grille

Place the mesh and grille on the top of the Radiance
stove to complete assembly.

Burner Information

The appliance must only use the gas specified on the
rating plate, unless converted using a Vermont Castings
Fuel Conversion Kit. To convert from LP to Natural Gas
use Kit #000-5009. To convert from Natural Gas to LP
use Kit #000-5010.
Conversion instructions are provided with each kit and
beginning on Page 29 in this manual.

THIS APPLIANCE SHOULD BE CON-

NECTED TO THE GAS SUPPLY ONLY BY

A QUALIFIED GAS SERVICE TECHNICIAN.

FOLLOW ALL LOCAL CODES.
THERE MUST BE A GAS SHUT-OFF BE-

TWEEN THE STOVE AND THE SUPPLY.

In order to connect Natural Gas, use a fitting with 1/2”
NPT on the valve side and 1/2” natural gas supply line
with an input of 35,000 BTUs at a manifold pressure
of 3.5” between minimum inlet supply of 5.5” w.c. and
maximum of 14.0” w.c.
In order to connect Propane, use a fitting with 1/2”
NPT on the valve side and 1/2” propane gas supply line
with an input of 35,000 BTUs at a manifold pressure of
10.0” between a minimum inlet supply of 11.0” w.c. and
maximum of 14.0” w.c.

This appliance should only be connected
by a qualified gas technician. Test to
confirm manifold pressures as specified
below.

The Radiance Heater and its individual shutoff
valve must be disconnected from the gas supply
piping during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The Radiance Heater must be isolated from the
gas supply piping system by closing its indi-
vidual manual shutoff valve during any pressure
testing of the gas supply piping system at test
pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove
and the supply.
In order to connect Natural Gas, use a fitting
with 1/2” NPT on the valve side and 1/2” natural
gas supply line with an input of 35,000 BTUs at a
manifold pressure of 3.5” between minimum inlet
supply of 5.5” w.c. and maximum of 14.0” w.c.
In order to connect Propane, use a fitting with 1/2”
NPT on the valve side and 1/2” propane gas sup-
ply line with an input of 35,000 BTUs at a manifold
pressure of 10.0” between a minimum inlet supply
of 11.0” w.c. and maximum of 14.0” w.c.

CAUTION

ST315

attach switch assy

1/31/00 djt

Switch As-

sembly

Screws

Existing

Holes

ST315

Fig. 42 Attach switch assembly to rear shroud.

Thermostat

Wire / Gauge

Maximum Run

18

20 feet

16

20 - 40 feet

14

up to 60 feet