Monarch Instrument ACT-3 User Manual

Page 12

Advertising
background image

AC OR TTL

SOURCE

WHITE

BLACK

BROWN

BLUE

BROWN
BLACK

BLUE

Shield to COM

Shield to COM

M-190W

Magnetic Sensor

or

SLS - Smart Laser Sensor

P5-11

Proximity Sensor

ROS-W - Optical Sensor
RLS-5W - Laser Sensor
IRS-W - Infrared Sensor
MT-190W - Amplified Mag Sensor
GE-200 - Gas Engine Sensor

AC or TTL

Source

LOAD

+

-

Pulse Output Option

Alarm Limits

Relay Connections

Outputs are dry

contact relays

CM = Common
NC = Normally Closed
NO = Normally Open

1 = Relay 1

2 = Relay 2

NC

NO

COM

7

Figure 3 Sensor Connections

2.4

Other Connections

Depending on how your unit is configured you may have TTL pulses, relay output or analog
output connections on the rear panel. Connection details for these options are shown in Figures
4 and 5.

Figure 4 PO and Relay Output Connections

(YELLOW - SLS)

(ORANGE- SLS)

16

@M1

Send Maximum value

Unit sends Maximum value once

@M2

Send Minimum value

Unit sends Minimum value once

@M3

Reset Max and Min

No Response

8.4

Control Commands

Control commands will STOP the instrument, as they require further input and basically alter
the operating parameters of the unit. Upon completion of the commands, the instrument will
continue. This may cause any currently set limits to be reset or to set.

CAUTION:

It is possible to set values into the unit with the Control commands
that could not be set from the front panel.

Once a command has been entered and accepted, the unit will respond with OK. This is an
indication that the instrument has stopped and is ready to accept the data. The words Err 8 will
appear on the instrument display to indicate RS232C control. The unit will remain stopped until
the command is completed.

The following are valid Control Commands. Enter the command and <CR>. Then enter the
follow-up command and <CR>.

Command

Action

Follow Up Action By User

@T1

Set operating mode

Enter a single character:
1 - Set mode = RPM (x60)
2 - Set mode = FREQUENCY (x1)
3 - Set mode = SCALING
4 - Set mode = SECAP
5 - Set mode = ROC
6 - Set mode = TOTALIZING
Followed by a <CR>.

@T2

Set decimal point

Enter either:
0 for fixed decimal point OR
1 for auto ranging
Followed by a <CR>.

@T3

Set scale factor

Enter a maximum of 6 digits with or without
a decimal point followed by a <CR>.
Recommended values are 0.0001 to 9999.9.

@T4

Set totalizer scale factor

Enter a maximum of 6 digits with or without
a decimal point followed by a <CR>.
Recommended values are 0.0001 to 9999.9.

@S1

Set Limit 1 mode

Enter a single character:
0 - Limit OFF
1 - Limit High, Latching
2 - Limit High, Auto Reset
3 - Limit Low, Latching, with Lockout
4 - Limit Low, Latching, no Lockout
5 - Limit Low, Auto Reset, with Lockout
6 - Limit Low, Auto Reset, no Lockout
Followed by a <CR>.

@S2

Set Limit 2 mode

Same as @S1 but for Limit 2.