Ace pump flow limiter, Figure 9 ace pump flow limiter, To install – Great Plains TSF1290 Predelivery Manual User Manual

Page 15

Advertising
background image

Preparation and Setup 13

11/08/2006

500-641Q

Ace Pump Flow Limiter

Refer to Figure 9

The flow limiter is a hydraulic device designed to shut
off the flow of hydraulic oil when a specified flow rate is
exceeded. On tractors with LOAD SENSING (LS)
Closed Center hydraulic systems, this device limits the
flow of oil to the Ace motor and prevents failures.

Newer Case-IH, John Deere, New Holland, and CAT
tractors have a great potential to run motors beyond
their rated speeds. Flows out of the hydraulic valves
can exceed 20 GPM while the motors are rated at 4-11
GPM. The flow limiter protects the Ace motor by shut-
ting off on excess hydraulic flow.

The flow limiter should not be used on OPEN center or
PRESSURE COMPENSATING Closed Center hydrau-
lic systems. The flow limiter should not be used with a
restrictor orifice.

To Install:
1.

Install the flow limiter in the inlet port of the Ace
motor.

2.

Connect the hydraulic hoses so that the pump runs
with the hydraulic lever in the “Lower/Retract” posi-
tion. Connect return hose to Low Pressure Return
Port, when available.

3.

Shut off boom and agitation valves on the sprayer to
deadhead the sprayer pump flow.

4.

Adjust the flow control on the tractor to minimum
flow setting (turtle).

5.

Move the hydraulic lever to the “Lower/Retract”
position.

Note: Always shut the pump off in the “Float” position.

This eliminates high pressure being trapped in
the return line and protects hydraulic seals. Avoid
returning the oil to the remote valve; use the Low
Pressure Return Port, when available.

6.

Adjust the flow control on the tractor until the
sprayer system deadhead pressure is within the
pump’s operating parameters:

Note: If the flow limiter stops the flow of oil to the motor

a.

Move the hydraulic lever to the “Neutral” posi-
tion. This removes the oil pressure from the flow
limiter and allows it to reset.

b.

Adjust the flow control to a lower flow position.

c.

Repeat steps 5 and 6.

7.

Set sprayer pressure by opening the agitation valve.

PTO Driven Pumps

a.

Open up the sprayer control valve to its maxi-
mum setting. (On the Raven 450 monitor, with
the power switch on, the rate switch must be
placed in the manual position, and the increase/
decrease switch must be pushed to increase for
10-12 seconds.)

b.

Start the tractor and engage the PTO pump
slowly with the tractor engine idling. Once the
system builds pressure on the pressure gauge,
shut off the boom section switched and close
the agitation valve.

c.

The pump is now at deadhead pressure.
Increase the engine RPM’s until the spray pres-
sure reaches 80 P.S.I. maximum on the pres-
sure gauge or the PTO speed reaches the rated
RPM (540/1000). Never exceed the rated trac-
tor PTO RPM. This is the RPM needed to spray
at to prevent excess pressure on the sprayer’s
plumbing.

8.

The sprayer is now ready to be calibrated. Refer to
the Operator’s Manual or Raven 450 Manual for
checking calibration depending on the control sys-
tem.

Figure 9

Ace Pump Flow Limiter

23395

Advertising