Troubleshooting Guide

Symptom

Cause

Corrective Action

An error code appears on

one or more display modules

The microprocessor detected a fault

and has shut down

Turn power switch to OFF position. Wait for at

least 5 seconds before turning on the power. The

program will reset itself.

Faulty wire connection between the

sensor and display module

Check error codes at the end of this section.

No power on the alarm

(no LED’s illuminated)

AC power not available

Ensure that the ON/OFF switch on the power

supply module is turned ON

AC wiring not connected

Check the building electrical breaker to ensure

that the power is ON

Check the voltage at the terminal block above

the transformer. Ensure that 115 VAC or 220 VAC

is being supplied.

Fuse is blown

Check the fuse. The fuse is located on the upper

right corner of the system power supply. Replace

the fuse if it is defective. See Appendix A.

DC power plug not connected to the

annunciator module

Ensure that the DC power plug is firmly in its

socket on the annunciator module.

Replace System Power Supply unit if all the above

steps fail to resolve the problem.

Defective ribbon cable

Replace the ribbon cable