Display functions – Amico Dome Loaded Manifold CSA User Manual

Page 11

Advertising
background image

www.amico.com

11

Display Functions

1. Introduce power to the control cabinet.

2. Follow Cylinder Changing Procedures on the side of the cabinet to ensure that all cylinders and fittings are secure

and properly connected to the header bar.

3. Check the indicator LED for proper functioning.

4. Only one Green LED, on the side which had its operating regulator set first, should be lit and the other side should

have a Yellow LED lit.

5. Close the cylinder valve on the primary bank and watch the indicator LED to ensure proper functioning. The primary

bank pressure should fall, while the secondary and line pressures stay constant.

6. When the primary pressure falls to approximately 120 PSI for all gases except Nitrogen 220 PSI the bank

switch-over occurs. The line pressure will remain constant with the LED display indicating the bank In Use.

7. With the Amico Automatic Gas Manifold wired up to the Amico Master Alarm, the changeover from primary

to secondary supply will cause an audible alarm buzzer and the appropriate indicator LED on the Master Alarm will
illuminate. This can also be achieved by using the switch-over test button located on the back of the control board.