Tank Level Sensing Processor and Sensors

Page 19

11

NMEA Output

To allow other equipment to interface with the TLSP, a NMEA sentence is transmitted
showing the levels in the tanks. The messages are transmitted using the XDR sentence.
Each tank output will have a separate NMEA message.

The format for the XDR message is below:

$YXXDR,V,0.095,M,1 P F BAL *HH<CR><LF>

Label Text

Sensor Input Number

Measurement Units

Measurement Data

Transducer Type

From the NMEA specification, the Talker ID is YX (Transducer). Transducer type is V,
(volume). The measurement data is M, in cubic meters (1000L = 1M

3

). The label text is a

mixture of the sensor input number and the text displayed on the FFD. The above sentence,
decoded reads a volume of 0.095M

3

(95L) from sensor input number 1, which has the FFD

text of ‘P F BAL

The output frequency of the messages is once per second. If the tank system has been setup
for percentage only, the output will be 0-100 litres (0-0.1 M

3

).

12

RS232 Interfacing

12.1

Input messages

Current tank levels are available through the RS232 port by sending the following message:

#OS,s<CR><LF>

s = 0 to stop automatic output.
s = 1 to start automatic output of all enabled sensor inputs.

12.2

Automatic Message Output

S,n,vol,c..c,a<CR><LF>

n

= sensor number

vol

= volume in tank

c..c

= FFD text

a

= alarm condition (A=Alarm, N=No Alarm)

In the case of OFF or Err being shown on the FFD the vol field will null.