Troubleshooting for initial installation – Baseline Systems WaterTec S100 User Manual

Page 12

Advertising
background image

● Connections need to be waterproof and free of corrosion
● Check biSensor wires for damage
● Check biSensor for damage

● After making repairs follow the "Verify biSensor
Communication" instructions under Step 1 at the end of this
section

Double-check the wiring and connections to the biSensor

● Verify connections inside the valve box are tight
● Check for a faulty valve solenoid
● Check for lightning damage

● Make sure the 24 VAC transformer is plugged in and
receiving power

● Check that the 24VAC line and the common line from the
S100 are wired correctly

Er2 is displayed

The S100 has detected excessive
current while trying to communicate
with the biSensor

Display is blank.
LED's are off

S100 is not receiving 24 VAC

Er1 is displayed

The S100 cannot communicate with
the biSensor

Er3 is displayed

Moisture Sensor is damaged

● Replace moisture sensor

11

WaterTec S100 Manual June08

Troubleshooting for Initial Installation

Problem

Cause

Solution

● This error is accompanied by one of the other error codes
● Refer to the other Er# for possible solutions

Er4 is displayed

There was a problem during the
S100 24-hour moisture threshold
calibration

● Follow the instructions under Step 5 at the end of this

section

● Make sure no extra water is applied to the biSensor after

calibration starts or the S100 may set a non-optimal threshold

Er5 is displayed
(This is a warning
message, pressing
“Read / Set” will
clear this)

Unexpected reading during 24-hour
moisture threshold calibration, final
reading was not substantially
different from the first (please refer
to the Er5 code on page 17)

Er6 is displayed

Unexpected low reading during
24-hour moisture threshold
calibration

● Rebury the biSensor as per Step 5 on page 8. When

reburying the biSensor be especially careful that NO rocks
are touching the blade of the biSensor as this can lead to
false readings

biSensor is reading a
value under 20.
Soil appears wet

There may be air pockets around
the biSensor

● Some older sprinkler controllers do not have access to

24 VAC; for more information on this go to
www.baselinesystems.com

Controller does not
have access to 24
VAC

Some older mechanical controllers

Follow the instructions under Step 5 at the end of this
section