Maintenance – Carrier 50JZ-A User Manual

Page 17

Advertising
background image

17

OF2

OF1

ON

QUIET

SHIFT

120

30

60

60

30

90

INTER

V

AL

TIMER

OFF

P3

DFT

O R

W

2

Y C

T2 C C O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A08020

Fig. 17 -- Defrost Control

Step 3 — Defrost Control

Quiet Shift

Quiet Shift is a field--selectable defrost mode, which will eliminate

occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3

(on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is

initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn

off for 30 sec and then turn back on to complete defrost. At the

start of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the

outdoor fan will stay off for 40 sec, before starting in the Heating
mode.

Defrost

The defrost control is a time/temperature control which includes a

field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

60 minutes). To initiate a forced defrost, two options are available

depending on the status of the defrost thermostat.
If defrost thermostat is closed, speed--up pins (J1) must be shorted

by placing a flat head screw driver in between for 5 sec and
releasing, to observe a complete defrost cycle. When the Quiet

Shift switch is selected, compressor will be turned off for two 30

sec intervals during this complete defrost cycle, as explained
previously. When Quiet Shift switch is in factory default OFF

position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are

shorted (with a flat head screw driver) for 5 sec and released, a

short defrost cycle will be observed (actual length is dependent
upon the selected Quiet Shift position). When Quiet Shift switch is

in ON position, the length of defrost is 1 minute (30 sec
compressor off period followed by 30 sec of defrost with

compressor operation). On return to heating operation, compressor

will again turn off for an additional 30 sec and the outdoor fan for
40 sec. When the Quiet Shift is in OFF position, only a brief 30

sec. cycle will be observed.
NOTE: Unit will remain in defrost until defrost thermostat
reopens at approximately 65_F +/-- 5_F (18_C +/-- 2.8_C) coil
temperature at liquid line or remainder of defrost cycle time.

MAINTENANCE

To ensure continuing high performance, and to minimize the

possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This heat pump unit should

be inspected at least once each year by a qualified service person.

To troubleshoot unit, refer to Table 7.
NOTE: TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.