Warning, Caution, Introduction – Carrier 50JZ-A User Manual

Page 2: Receiving and installation, Step 1 — check equipment, Step 2 — provide unit support, Step 3 — provide clearances

Advertising
background image

2

signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies

the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in per-

sonal injury or death. CAUTION is used to identify unsafe practic-

es which may result in minor personal injury or product and prop-
erty damage. NOTE is used to highlight suggestions which will

result in enhanced installation, reliability, or operation.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system and install lockout tag. There may be

more than one disconnect switch. Turn off accessory heater

power switch if applicable.

!

WARNING

CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 18) or performing

maintenance functions inside your unit, be aware of sharp

sheet metal parts and screws. Although special care is taken

to reduce sharp edges to a minimum, be extremely careful

when handling parts or reaching into the unit.

!

CAUTION

INTRODUCTION

The 50JZ--A heat pump is fully self--contained and designed for

outdoor installation. (See Fig. 1) Standard units are shipped in a
horizontal--discharge configuration for installation on a ground

level slab. Standard units can be converted to downflow (vertical)

discharge configurations for rooftop applications.

RECEIVING AND INSTALLATION

Step 1 — Check Equipment

Identify Unit

The unit model number and serial number are stamped on the unit

identification plate. Check this information against shipping
papers.

Inspect Shipment

Inspect for shipping damage before removing packaging material.

If unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.

Forward claim papers directly to transportation company.

Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the

nearest equipment distributor if any item is missing. To prevent
loss or damage, leave all parts in original packages until

installation.
If the unit is to be mounted on a curb in a downflow application,

review Step 5 to determine which method is to be used to remove

the downflow panels before rigging and lifting into place. The
panel removal process may require the unit to be on the ground.

Step 2 — Provide Unit Support

Roof Curb

Install accessory roof curb in accordance with instructions shipped

with curb (See Fig. 5). Install insulation, cant strips, roofing, and
flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasketing material supplied with the

roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.
Curb should be level to within 1/4 in. (6 mm) (See Fig. 9). This is

necessary for unit drain to function properly. Refer to accessory

roof curb installation instructions for additional information as
required.
Installation on older “G” series roof curbs.
Two accessory kits are available to aid in installing a new “G”

series unit on an old “G” roof curb.

1. Accessory kit number CPADCURB001A00, (small chassis)

and accessory kit number CPADCURB002A00, (large
chassis) includes roof curb adapter and gaskets for the

perimeter seal and duct openings. No additional
modifications to the curb are required when using this kit.

2. An alternative to the adapter curb is to modify the existing

curb by removing the outer horizontal flange and use
accessory kit number CPGSKTKIT001A00 which includes

spacer blocks (for easy alignment to existing curb) and
gaskets for the perimeter seal and duct openings. This kit is
used when existing curb is modified by removing outer

horizontal flange.

UNIT/STRUCTURAL DAMAGE HAZARD
Failure to follow this caution may result in property

damage.
Ensure there is sufficient clearance for saw blade when

cutting the outer horizontal flange of the roof curb so there

is no damage to the roof or flashing.

!

CAUTION

Slab Mount

Place the unit on a solid, level concrete pad that is a minimum of 4

in. (102 mm) thick with 2 in. (51 mm) above grade (See Fig. 2).
The slab should extend approximately 2 in. (51 mm) beyond the

casing on all 4 sides of the unit. Do not secure the unit to the slab
except when required by local codes.

OPTIONAL

RETURN

AIR

OPENING

OPTIONAL

SUPPLY

AIR

OPENING

EVAP. COIL

COND. COIL

(50.8mm)

A07926

Fig. 2 -- Slab Mounting Detail

Step 3 — Provide Clearances

The required minimum service clearances are shown in Fig. 3 and
4. Adequate ventilation and outdoor air must be provided. The

outdoor fan draws air through the outdoor coil and discharges it

through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a

corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48

in. (1219 mm) above the unit top. The maximum horizontal

extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang

or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units

50J

Z

--

A

Advertising