Step 3 — outdoor fan, Step 4 — electrical controls and wiring, Step 5 — refrigerant circuit – Carrier 50JZ-A User Manual

Page 19: Step 6 — indoor airflow, Step 7 — metering device -- piston, Step 8 — pressure switches, Step 9 — loss of charge switch

Advertising
background image

19

Step 2 — Outdoor Coil, Indoor Coil, and

Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain

pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean

the coils either before or after each cooling season. Remove all

obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush

attachment. Be careful not to bend the fins. If coated with oil or

grease, clean the coils with a mild detergent--and--water solution.
Rinse coils with clear water, using a garden hose. Be careful not to

splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit. On

units with an outer and inner condenser coil, be sure to clean

between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all

foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or

air filter(s). If the drain tube is restricted, clear it with a plumbers

snake or similar probe device.

Step 3 — Outdoor Fan

Keep the condenser fan free from all obstructions to ensure

proper cooling operation. Never place articles on top of the
unit. Damage to unit may result.

1. Remove 6 screws holding outdoor grille and motor to top

cover.

2. Turn motor/grille assembly upside down on top cover to

expose fan blade.

3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off

motor shaft.

5. When replacing fan blade, position blade back to same posi-

tion as before.

6. Ensure that setscrew engages the flat area on the motor shaft

when tightening.

7. Replace grille.

Step 4 — Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panels (see Fig. 18) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.

Tighten all screw connections. If any discolored or burned

connections are noticed, disassemble the connection, clean all the
parts, restrip the wire end and reassemble the connection properly

and securely.
After inspecting the electrical controls and wiring, replace all the

panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in

operating cycle, or if a suspected malfunction has occurred, check

each

electrical

component

with

the

proper

electrical

instrumentation. Refer to the unit wiring label when making these

checkouts.

Step 5 — Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil

accumulation annually. Detecting oil generally indicates a

refrigerant leak.
If oil is detected or if low performance is suspected, leak--test all

refrigerant tubing using an electronic leak detector, or liquid--soap

solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.

Step 6 — Indoor Airflow

The heating and/or cooling airflow does not require checking

unless improper performance is suspected. If a problem exists, be
sure that all supply--air and return--air grilles are open and free

from obstructions, and that the air filter is clean. When necessary,
refer to Indoor Airflow and Airflow Adjustments section to check

the system airflow.

Step 7 — Metering Device -- Piston

This unit uses a fixed orifice metering device for both cooling and
heating modes.

C99097

Fig. 19 -- Refrigerant Circuit

Step 8 — Pressure Switches

Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnormally high or low

pressures are present in the refrigeration circuit. These pressure
switches are specifically designed to operate with Puron (R--410A)

systems. R--22 pressure switches must not be used as replacements

for the Puron (R--410A) system.

Step 9 — Loss of Charge Switch

This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low
airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig (138 kPa). If system pressure is above this,
switch should be closed. To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

NOTE:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.

50J

Z

--

A

Advertising