5 technical data – Baumer PA200 User Manual

Page 19

Advertising
background image

PA200

www.baumer.com

19

4.3 Programming lock
Programming access depends on the selected input configuration.

1. Voltage 20 or 200 V: Press and hold for 5.

Enter 0 or 1 in line„LC“.

2. All other input configurations provide access rights at the end of

display configuration as follows:

After parameterization of „dSP2“ press and hold for 5 s.

Enter 0 or 1 in line „LC“.

Programming lock disabled

Programming lock enabled

Programming lock means programming lines are read only which will

be signaled by [dAtA] instead of [Pro] appearing in the display when

accessing programming level.

5 Technical data

Technical data - electrical ratings

Voltage supply

21...53 VAC (50/60 Hz) or

10.5...70 VDC

85...265 VAC (50/60 Hz) or

100...300 VDC

Power consumption

1.8 W

Display

LED, 7-segment display (with 60 unit

stickers for front)

Number of digits

4-digits

Digit height

10 mm

Display range

-1999...9999 („OuE“ to signal

overflow)

Display refresh

250 ms

A/D transformer

Principle ∑∆

Resolution 16 bit

Measuring rate 20/s

Measuring accuracy ±(0.1 % +3 digit)

Temp. coeffic. 100 ppm/°C

Analog input

Current or voltage input

Programmable

Measuring range

parameters

Display range can be linearised

Decimal point

Data memory

>10 Jahre in EEPROM

Standard

Protection class II

DIN EN 61010-1

Overvoltage category II

Pollution degree 2

Emitted interference

DIN EN 61000-6-3

Interference immunity

DIN EN 61000-6-2

Advertising