APPENDIX B — CCN TABLES (cont)

SERVICE-CONFIG TABLES (cont)

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

DEFAULT

IAQ_

Economizer Min.Position

0 - 100

%

ECONOMIN

5

IAQ Demand Vent Min.Pos.

0 - 100

%

IAQMINP

0

Economizer Min.Flow

0 - 20000

CFM

OACFMMAX

2000

IAQ Demand Vent Min.Flow

0 - 20000

CFM

OACFMMIN

0

Econ.Min.Flow Deadband

200 - 1000

CFM

OACFM_DB

400

IAQ Analog Sensor Config

0 - 4

IAQANCFG

0

IAQ 4-20 ma Fan Config

0 - 2

IAQANFAN

0

IAQ Discrete Input Config

0 - 2

IAQINCFG

0

IAQ Disc.In. Fan Config

0 - 2

IAQINFAN

0

OAQ 4-20ma Sensor Config

0 - 2

OAQANCFG

0

IAQ Econo Override Pos.

0 - 100

%

IAQOVPOS

100

IAQ Override flow

0 - 31000

CFM

IAQOVCFM

10000

Diff.Air Quality LoLimit

0 - 1000

DAQ_LOW

100

Diff. Air Quality HiLimit

100 - 2000

DAQ_HIGH

700

DAQ PPM Fan Off Setpoint

0 - 2000

DAQFNOFF

200

DAQ PPM Fan On Setpoint

0 - 2000

DAQFNON

400

Diff. AQ Responsiveness

-5 - 5

IAQREACT

0

OAQ Lockout Value

0 - 2000

OAQLOCK

0

User determined OAQ

0 - 5000

OAQ_USER

400

IAQ Low Reference

0 - 5000

IAQREFL

0

IAQ High Reference

0 - 5000

IAQREFH

2000

OAQ Low Reference

0 - 5000

OAQREFL

0

OAQ High Reference

0 - 5000

OAQREFH

2000

IAQ Purge

Yes/No

IAQPURGE

No

IAQ Purge Duration

5-60

min

IAQPTIME

15

IAQ Purge LoTemp Min Pos

0-100

%

IAQPLTMP

10

IAQ Purge HiTemp Min Pos

0-100

%

IAQPHTMP

35

IAQ Purge OAT Lockout

35-70

dF

IAQPNTLO

50

SP__

Static Pressure Config

0 - 2

STATICFG

0

Static Pressure Sensor

Enable/Disable

SPSENS

Disable

Static Press. Low Range

-10 - 0

SP_LOW

0

Static Press. High Range

0 - 10

SP_HIGH

5

Static Pressure Setpoint

0 - 5

"H2O

SPSP

1.5

VFD-IGV Minimum Speed

0 - 100

%

STATPMIN

10

VFD-IGV Maximum Speed

0 - 100

%

STATPMAX

100

VFD-IGV Fire Speed Over.

0 - 100

%

STATPFSO

100

Stat. Pres. Reset Config

0 - 4 (multi-text strings)

SPRSTCFG

0

SP Reset Ratio

0.00 - 2.00

SPRRATIO

0.20

SP Reset Limit

0.00 - 2.00

SPRLIMIT

0.75

SP Reset Econo. Position

0 - 100

%

ECONOSPR

5

Stat.Pres.PID Run Rate

5 - 120

sec

SPIDRATE

15

Static Press. Prop. Gain

0 - 5

STATP_PG

0.5

Static Press. Intg. Gain

0 - 2

STATP_IG

0.5

Static Press. Derv. Gain

0 - 5

STATP_DG

0.3

IGV Serial Number 1

0 - 255

IGV_SN1

0

IGV Serial Number 2

0 - 255

IGV_SN2

0

IGV Serial Number 3

0 - 255

IGV_SN3

0

IGV Serial Number 4

0 - 255

IGV_SN4

0

IGV Serial Number 5

0 - 255

IGV_SN5

0

IGV Cntrl Angle Lo Limit

0-90

IGV_CALM

25

SWLG

Filter Status Inpt-Clean

Open/Close

FLTSLOGC

Open

IGC Feedback - Off

Open/Close

GASFANLG

Open

RemSw Off-Unoc-Strt-NoOv

Open/Close

RMTINLOG

Open

Enthalpy Input - Low

Open/Close

ENTHLOGC

Close

Fan Status Sw. - Off

Open/Close

SFSLOGIC

Open

Dmd.Lmt.Sw.1 - Off

Open/Close

DMD_SW1L

Open

Dmd.Lmt.Sw.2 - Off

Open/Close

DMD_SW2L

Open

IAQ Disc.Input - Low

Open/Close

IAQINLOG

Open

Fire Shutdown - Off

Open/Close

FSDLOGIC

Open

Pressurization Sw. - Off

Open/Close

PRESLOGC

Open

Evacuation Sw. - Off

Open/Close

EVACLOGC

Open

Smoke Purge Sw. - Off

Open/Close

PURGLOGC

Open

Dehumidify Sw. - Off

Open/Close

DHDISCLG

Open

TRIM

Air Temp Lvg SF Trim

-10 - 10

^F

SAT_TRIM

0

RAT Trim

-10 - 10

^F

RAT_TRIM

0

OAT Trim

-10 - 10

^F

OAT_TRIM

0

SPT Trim

-10 - 10

^F

SPT_TRIM

0

Limit Switch Trim

-10 - 10

^F

LSW_TRIM

0

Air Temp Lvg Evap Trim

-10 - 10

^F

CCT_TRIM

0

Suct.Press.Circ.A Trim

-50 - 50

SPA_TRIM

0

Suct.Press.Circ.B Trim

-50 - 50

SPB_TRIM

0

Dis.Press.Circ.A Trim

-50 - 50

DPA_TRIM

0

Dis.Press.Circ.B Trim

-50 - 50

DPB_TRIM

0

Static Press. Trim (ma)

-2 - 2

SPMATRIM

0

Bldg. Pressure Trim (ma)

-2 - 2

BPMATRIM

0

Outside Air CFM Trim (ma)

-2 - 2

OAMATRIM

0

Supply Air CFM Trim (ma)

-2 - 2

SAMATRIM

0

Return Air CFM (ma)

-2 - 2

RAMATRIM

0