Controlling high-capacity power exhaust differs from nor-

mal power exhaust in the following ways:
• The integral term is not used. The percentile commanded

position of the VFD is used instead.

• A “clamp percent” configuration is added (BP.CL) to

create a deadband that will assist the algorithm in

controlling the second power exhaust relay.
If building pressure (BP) rises above the building pressure

set point (BP.SP) and the supply fan is on, building pressure

control is initiated. Thereafter if the supply fan relay goes off or

if the building pressure drops below the BP.SP minus the

building pressure set point offset (BP.SO) for 5 continuous

minutes, building pressure control will be stopped. The

5-minute timer will continue to reset while the VFD is com-

manded to a position > 0%. If the building pressure falls below

the set point, the VFD will shut down automatically. Any time

building pressure control becomes active, the exhaust fan relay

turns on which energizes the exhaust fan VFD.
After the exhaust fan relay turns on, PID control ensues with-

out an “I” term:
Error = BP – BP.SP
K = 1000 * BP.TM / 60 (normalize the PID control for run rate)
P = K * BP.P * (error)
D = K * BP.D * (error - error computed last time through the

PID)
VFD control signal (clamped between 0 and 100%) = VFD

Output last time through + (P + D)
NOTE: The sum of P + D will be clamped on any timed calcu-

lation to an internally calculated value which guarantees the

VFD is not commanded more or less an amount, than it cannot

achieve before the next time VFD capacity is again calculated.

Bringing the single speed fan (P.E.2) ON and OFF is coordi-

nated with the VFD speed. When building pressure first

becomes active, P.E.2 is OFF, P.E.1 is ON and the VFD is

allowed to climb to 100%. BP.CL will be used to act as hyster-

esis so that when the P + D term is evaluated and it exceeds

BP.CL, the control will go through a one-minute period hold

off time where the VFD is commanded to BP.CL, and P.E.2 is

brought on. After the transition to P.E.2 ON is complete, the

control will continue to control the VFD from BP.CL%. If BP

rises, the control will speed up the VFD. Should the VFD drop

to 0%, and the next time through the PID the P + D term calcu-

lation is less than – BP.CL, the control will go through another

one-minute PID hold off period where P.E.2 is commanded

OFF and the VFD is commanded to 100 – BP.CL.
Configuration

BP

BP.CF =5 (Return/Exhaust Control)

— Fan tracking is the method of control used on plenum return

fan option. The fan tracking algorithm controls the exhaust/

return fan VFD and the exhaust fan relay. The ComfortLink™

controls use a flow station to measure the flow of both the sup-

ply and the return fans. The speed of the return fan is controlled

by maintaining a delta cfm (usually with supply airflow being

greater of the two) between the two fans. The building pressure

is controlled by maintaining this delta cfm between the two

fans. In general, the greater the delta between supply airflow

and return airflow, the higher the building pressure will be.

Conversely, as the return airflow quantity increases above

the supply airflow, the lower the building pressure will be.

Whenever there is a request for the supply fan (or there is the

presence of the IGC feedback on gas heat units), the return fan

is started. The delta cfm is defined as S.CFMR.CFM. The

return fan VFD is controlled by a PID on the error of delta cfm

actual from delta cfm set point. If the error is positive the drive

will increase speed. If the error is negative the drive will

decrease speed.
NOTE: These configurations are used only if Fan Tracking

Learning is enabled. When Fan Tracking Learning is enabled,

the control will adjust the delta cfm (FT.ST) between the

supply and return fan if the building pressure deviates from the

Building Pressure Set Point (BP.SP). Periodically, at the rate

set by the fan track learn rate (FT.TM), the delta cfm is

adjusted upward or downward with a maximum adjustment

at a given instance to be no greater than fan track max

correction (FT.AD). The delta cfm can not ever be adjusted

greater than or less than the fan track initial delta cfm (FT.ST)

than by the Fan Track Max Clamp (FT.MX).
CONFIGURING THE BUILDING PRESSURE ACTUA-

TORS (BP.CF = 2) TO COMMUNICATE VIA ACTUATOR

SERIAL NUMBER — Every actuator used in the Z Series

control system has its own unique serial number. The rooftop

control uses this serial number to communicate with the

actuator over the local equipment network (LEN). These serial

numbers are programmed at the factory and should not need

changing. Should field replacement of an actuator become

necessary, it will be necessary to configure the serial numbers

of the new actuator. Five individual numbers make up each se-

rial number and these can be programmed to match the serial

number of the actuators in the building pressure actuator

configurations group, ACT.C.

BP.1 and BP.2 (SN.1, SN.2,

SN.3, SN.4, SN.5).
NOTE: The serial numbers for all LEN actuators can be found

inside the control doors of the unit as well as on the actuator

itself. If an actuator is replaced in the field, it is a good idea to

remove the additional peel-off serial number sticker on the

actuator and cover up the old one inside the control doors.
CONTROL ANGLE ALARM CONFIGURATION C.ALM

(BP.CF = 2) — The building pressure actuators learn what its

end stops are though a calibration at the factory. Field-installed

actuators may be calibrated in the Service Test mode. When an

actuator learns its end stops through calibration, it stores the

control angle. The actuator will resolve this control angle and

express its operation in a percent (%) of this learned range.

If a building pressure actuator has not learned a sufficient

control angle during calibration, the actuator will be unable to

control building pressure. For this reason the building pressure

actuators used in the Z Series control system have configurable

control angle alarm low limits in the Building Pressure Actua-

tor Configurations group, ACT.C

BP.1 and BP.2. (C.A.LM).

If the control angle learned through calibration is less than

C.A.LM, an alert will occur and the actuator will not function.
NOTE: This configuration does not typically need adjustment.

It is configurable for the small number of jobs which may

require a custom solution or workaround.

Smoke Control Modes —

There are four smoke con-

trol modes that can be used to control smoke within areas ser-

viced by the unit: Pressurization mode, Evacuation mode,

Smoke Purge mode, and Fire Shutdown. Evacuation, Pressur-

ization and Smoke Purge modes require the controls expansion

board (CEM). The Fire Shutdown input is located on the main

board (MBB) on terminals TB201-5 and 6. The unit may also

be equipped with a factory-installed return air smoke detector

that is wired to TB201-5,6 and will shut the unit down if a

smoke condition is determined. Field-monitoring wiring can be

connected to terminal TB201-13 and 14 to monitor the smoke

detector. Inputs on the CEM board can be used to put the unit

in the Pressurization, Evacuation, and Smoke Purge modes.

These switches or inputs are connected to TB204 as shown be-

low. Refer to Major System Components section on page 102

for wiring diagrams.
Pressurization — TB204-5 and 6
Evacuation — TB204-7 and 8
Smoke Purge — TB204-9 and 10

Each mode must be energized individually on discrete in-

puts and the corresponding alarm is initiated when a mode is

activated. The fire system provides a normally closed dry