Stardance natural vent gas heater – Vermont Casting SNV30 User Manual

Page 15

Advertising
background image

15

Stardance Natural Vent Gas Heater

20007067

A. Defective or misaligned

Using a match, light [ilot. If pilot lights, turn off pilot and

electrode at the pilot

push the ignitor button again. If pilot will not light, check

gap at electrode and pilot - it should be 1/8” to have a

strong spark.

B. Defective ignitor (push

Push piezo ignitor button. Check for spark at electrode

button)

and pilot. If there is no spark at the pilot, and electrode

wire is properly connected, replace ignitor.

A. Defective pilot generator

Check pilot flame. It must impinge on the thermocouple

(thermocouple)

or thermopile. NOTE: This pilot burner assembly uses

both a thermocouple adn a thermopile. The thermo-

couple operates the pilot flame. Tighten the thermo-

couple. The thermopile operates the main valve. (ON

and OFF) Clean and/or adjust pilot for maximum flame

impingement on thermocouple and thermopile.

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot; millivolt

operator

mete should read greater than 10mV. If the reading is

okay and the pilot does not stay on, replace the gas

valve. NOTE: An interrupter block (not supplied) must

be used to conduct this test.

C.Defective safety switch

Check the continuity accross the safety limit switch with

the unit cold. If there is no continuity, the safety switch

needs to be replaced.

A. Remote switch or wires

Check rocker switch and wires for proper connection

defective

Use jumper wires across terminals at rocker switch. If

burner lights, replace rocker switch. If okay, use jumper

wires across rocker switch wires at the valve. If burner

lights, wires are faulty or connections are bad.

B. Thermopile may not gen-

1. Be sure wire connecitons from thermopile at gas

ate sufficient voltage

valve terminals are tight and thermopile is fully inserted

into pilot bracket.

2. One of the rocker switch wires may be grounded

Remove rocker switch wire form valve termianls. If

burner now stays lit, trace rocker switch wiring from

ground. It may be grounded to the appliance of the

gas supply line.

3. Check the thermopile with a millivolt meter. Take

reading at thermopile (“TP” and “TP/TH”) terminals of

gas valve. Should read 325 millivolts minimum while

holding valve knob depressed in PILOT position and

with rocker switch OFF. Replace faulty thermopile if

reading is below specified minimum.

C. Plugged burner orifice

Check burner orifices for debris, and remove.

D. Defective automatic valve

Turn knob to ON, place rocker switch to ON. Millivolt

operator

meter should read greater than 10mV. If the reading is

okay and the burner does not light, replace the valve.

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

or high, (blowing or lifting).

impingement on thermocouple and thermopile.

causing the pilot to drop out
B. Possible blockage of the

Check the vent termianl for blockage.

vent terminal

Troubleshooting / Honeywell #8420 Gas Control System

NOTE: Before troubleshooting the gas control system, be sure the external gas shutoff is in the “ON” position.

WARNING: REMOVE THE GLASS PANEL BEFORE PERFORMING ANY GAS CONTROL SERVICE WORK.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark ignitor will

not light

2. Pilot will not stay lit

after carefully fol-
lowing the lighting
instructions

3. Pilot lights, no gas

to burner, valve
knob ON, remote
switch (rocker
switch) ON

4. Frequent pilot out-

age

Advertising