Venting runs, Stardance natural vent gas heater, Passing through a combustible wall or ceiling – Vermont Casting SNV30 User Manual

Page 7: Venting requirements

Advertising
background image

7

Stardance Natural Vent Gas Heater

20007067

Passing Through a

Combustible Wall or Ceiling

An approved pass-through device is always required
when a vent passes through a combustible wall or ceil-
ing. Check with the maker of the vent system for the
correct listed devices that are available. A listed pass-
through device is required whether or not the installa-
tion includes decorative pipe around the Type B venting
system. NOTE: It is essential to seal between the ceil-
ing support (sometimes called a ‘firestop spacer’) and
the decorative pipe, if installed, with a high-temperature
silicone sealant. (Fig. 6)
Complete the venting system installation according to
the manufacturer’s instructions.

ST361

Ceiling pass thru

5/11/00 djt

Joists

Ceiling

Support

Trim Col-

lar

Air Space

Listed 4”

(102 mm)

B-Vent

Decorative

6” Pipe

High-tempera-

ture Silicone

Sealant

Air Space as Re-

quired by Code

ST361

Fig. 6 A ceiling pass-through, with decorative pipe around the

vent.

High-tem-

perature

Silicone

Sealant

Fig. 7 Vent termination window.

Venting Requirements

FP567
NVBR/NVBC VENTING RUNS
11/12/97

Venting Runs

A: Vertical installations up to 36 feet (12m) in

height. Up to an 18 ft. horizontal vent run can be

installed within the vent system using a

maximum of two 90-degree elbows or four

45-degree elbows.

B: Vertical installations up to 36 feet (12m) in

height. Up to a 24 ft. horizontal vent run can be

installed within the vent system using a

maximum of two 45-degree elbows.

(Ratio = 2/3, Hor./Vert.)

= Acceptable venting configuration
= Unacceptable venting configuration

NOTE: When venting staight vertical, without an

elbow, a minimum of 8 ft. vertical is required

off the top of the stove.

Horizontal Run (in feet)

Vertical Run (in feet)

(Measured from top of the unit before any elbow

)

36
34
32
30
28
26
24
22
20
18
16
14
12
10

8
6
4
2

1 2 4 6 8 10 12 14 16 18 20 22 24

A

B

FP567b