Cooper Bussmann CT02MAN User Manual

Page 29

Advertising
background image

27

Cable Tray Manual

Cooper B-Line, Inc

Ground Bus

Bonded To

Enclosure

EGC

EGC In

Cable

Discontinuous Joints

Require Bonding

For Qualifying Facilities

EGCs in the Cables or

EGC Cables Are Not

Required If Rating Of The

Feeder Overcurrent Device

Permits Using The Tray

For the EGC

Bonding Jumper Not

Required For Rigidly

Bolted Joints

Conduit

Three Phase

Motor Installation

Building Steel

Lightning

Protection

Grounding

Bond

Switchgear

Bond

System Ground

Transformer

(Solidly

Grounded

Secondary)

Motor Control Center

Correct Bonding Practices To Assure That The

Cable Tray System Is Properly Grounded

If an EGC cable is installed in or on a cable tray, it should be bonded to each or alternate cable

tray sections via grounding clamps (this is not required by the NEC

®

but it is a desirable practice). In

addition to providing an electrical connection between the cable tray sections and the EGC, the
grounding clamp mechanically anchors the EGC to the cable tray so that under fault current
conditions the magnetic forces do not throw the EGC out of the cable tray.

A bare copper equipment grounding conductor should not be placed in an aluminum cable tray

due to the potential for electrolytic corrosion of the aluminum cable tray in a moist environment.
For such installations, it is best to use an insulated conductor and to remove the insulation where
bonding connections are made to the cable tray, raceways, equipment enclosures, etc. with tin or
zinc plated connectors.

See Table 250.122 on page 51

for the minimum size EGC for

grounding raceway and equipment.

Advertising