Technically desirable installation – Cooper Bussmann CT02MAN User Manual

Page 39

Advertising
background image

392.11. Ampacity of Cables Rated 2000
Volts or Less in Cable Trays. (B) Single
Conductor Cables.

Single conductor cables can be installed in a cable

tray cabled together (triplexed, quadruplexed, etc.) if
desired. Where the cables are installed according to
the requirements of Section 392.10, the ampacity
requirements are shown in the following chart as
per Section 392.11(B)(1), (2), (3), & (4):

392.12. Number of Type MV and Type
MC Cables (2001 Volts or Over) in Cable
Trays.

Sum the diameters of all the cables (Sd) to

determine the minimum required cable tray width.
Triplexing or quadruplexing the cables does not
change the required cable tray width. Whether the
cables are grouped or ungrouped, all installations
must be in a single layer.

392.13. Ampacity of Type MV and Type
MC Cables (2001 Volts or Over) in Cable
Trays. (A) Multiconductor Cables (2001
Volts or Over).

Provision No. 1: Where cable trays are

continuously covered for more than six feet
(1.83 m) with solid unventilated covers, not
more than 95% of the allowable ampacities
of Tables 310.75 and 310.76 shall be
permitted for multiconductor cables.

Cables installed in cable trays with solid

unventilated covers must be derated. Where cable
tray covers are to be used, it is best to use raised or
ventilated covers so that the cables can operate in a
lower ambient temperature.

37

Cable Tray Manual

Cooper B-Line, Inc

Mult.

Solid

Applicable

Amp.

Sec.

Cable

Unventilated

Ampacity

Table

Special

No.

Sizes

Cable Tray

Tables

Values

Conditions

Cover

(*)

By

600 kcmil

No Cover

310.17

(1)

and

Allowed

and

0.75

Larger

(**)

310.19

600 kcmil

310.17

(1)

and

Yes

and

0.70

Larger

310.19

1/0 AWG

No Cover

310.17

(2)

through

Allowed

and

0.65

500 kcmil

(**)

310.19

1/0 AWG

310.17

(2)

through

Yes

and

0.60

500 kcmil

310.19

1/0 AWG

Maintained

(3)

& Larger

No Cover

310.17

1.00

Spacing Of

In Single

Allowed

and

One Cable

Layer

(**)

310.19

Diameter

Single

Conductors

310.20

Spacing Of

(4)

In Triangle

No Cover

[See NEC

2.15 x One

Config.

Allowed

Section

1.00

Conductor

1/0 AWG

(**)

310.15(B)]

O.D. Between

and Larger

Cables(***)

(*) The ambient ampacity correction factors must be used.

(**) At a specific position, where it is determined that the tray
cables require mechanical protection, a single cable tray cover of
six feet or less in length can be installed.

The wording of Section 392.11(B)(4) states that a spacing of
2.15 times one conductor diameter is to be maintained between
circuits. Two interpretations of this statement are possible.
Interpretation #1. - The 2.15 times one conductor diameter is
the distance between the centerlines of the circuits (the center
lines of the conductor bundles). Interpretation #2. - The 2.15
times one conductor diameter is the free air distance between the
adjacent cable bundles. The use of the word “circuit” is
unfortunate as its presence promotes Interpretation #1. An
installation based on Interpretation #1 is not desirable as a free
air space equal to 2.15 times one conductor diameter between
the cable bundles should be maintained to promote cable heat
dissipation.

Spacing Between Conductors
(2.15 x O.D. of Conductor)

Technically Desirable Installation

Spacing Between Conductors
(2.15 x O.D. of Conductor)

Technically Undesirable Installation

Interpretation #1

Interpretation #2

Advertising