51

Cable Tray Manual

Cooper B-Line, Inc

Appendix Sheet 7

Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright© 1998, National Fire

Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National
Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.

Table 250.122. Minimum Size Equipment Grounding
Conductors for Grounding Raceways and Equipment

Rating or Setting of

Size

Automatic Overcurrent

(AWG or kcmil)

Device in Circuit Ahead

of Equipment, Conduit,

Aluminum or

etc., Not Exceeding

Copper-Clad

(Amperes)

Copper

Aluminum*

15

14

12

20

12

10

30

10

8

40

10

8

60

10

8

100

8

6

200

6

4

300

4

2

400

3

1

500

2

1/0

600

1

2/0

800

1/0

3/0

1000

2/0

4/0

1200

3/0

250

1600

4/0

350

2000

250

400

2500

350

600

3000

400

600

4000

500

800

5000

700

1200

6000

800

1200