• The unit control circuit only allows opening of the motorized

valve when the fan motor is working.
(See wiring diagrams)

• When the thermostat asks for cooling, terminal 1 of TB3 (cold

water) is supplied with 230V.
When it asks for heating, terminal 2 of TB3 (hot water or
electric heater) is supplied with 230V.

• The control circuit ensures that the condensate discharge

pump works continuously while the thermostat, asking for
cooling, keeps the cold water regulating valve open.

WARNING :
The valve is not only necessary to control the room
temperature, but also to stop the cold water flow to the coil
in case of an abnormal condensing water level rise in the
drain pan.

• If there is an abnormal condensing water rise in the drain pan

(for example: possible defective drain, pump malfunction, fan
motor not working) causing the opening of the float switch
contact (FS), the control circuit either operates the c
ondensate drain pump, or at the same time closes the
regulating valve, stopping the cold water flow towards the
coil and avoiding further condensation.

Control

The water flow has to be controlled:
by installing the motorized thermo-electric valves supplied

as accessory

or
by installing motorized field supplied valves.

Motorized valve and control

Assembly

For models 42GWD (4-pipe), the valve assembly for the
cold water coil must be installed first.
• Gently grease the O-rings before fitting them into their

seats.

• Connect the valve assemble to the coil and fix it by a 30Nm

torque.

• Insulate the valve assembly.

• For 4-pipe hot water coil, repeat all the operations with gas

adaptors, as per the table.

• Pass cables through the cable holder G and fix them to the

case using the already pre-assembled screws.

• Mount the drain pan below the valve assembly, inserting the

discharge pipe into the special hole; align and fix it to the 3
clips previously assembled using the three screws supplied.

• Insulate the 3 screws and the drain pan lower part using the

insulating material F.

• To connect the steel pipes to the system, ensure they are

aligned and supported to avoid excess strain on the unit. If
the system is filled with water, check all fitting seals.

NOTE:
The seal efficiency of the valve assembly is factory tested.
Any system losses are therefore due to an incorrect
installation.

Electric connections

• To connect valves to the electric panel pass cables through

the electric panel grommet and connect them to the terminal
board TB3 as per the wiring diagrams.

Instructions for mounting of motorized
thermo-electric valve assembly

(see "Components" table)

• The thermo-electric valve must be mounted on the unit after

the unit installation.
For this operation follow figures, depending on model.

• Insert the clips supplied in the unit side slots.

004

012

004

020

Mod. 42GW

008

016

010

010

020

2-pipe

4-pipe

Ref. Description

q.ty

q.ty

q.ty

q.ty

A

Adaptor 3/4 " gas with O-ring

2

Adaptor 1" gas with O-ring +

2+

Adaptor 3/4" gas with O-ring +

2

B

Self tapping screw

3

3

3

3

C

Clip

3

3

3

3

D

Valve 1" gas pre-assembled

1

Valve 1" gas pre-assembled +

1+

Valve 3/4" gas pre-assembled

1

D1

Valve 3/4" gas pre-assembled

1

Valve 3/4" gas pre-assembled

1+

Valve 1/2" gas pre-assembled

1

E

Auxiliary drain pan

1

1

1

1

F

Insulating material

1

1

1

1

G

Cable holder

1

1

1

1

D1

Water inlet

Water outlet

Motorized thermo-electric valve assembly and components

Adaptor

O-ring

Coil coupling

Fit the reducers and O-rings
towards the coil connection.

ቤ ብ ቦ

G

E

A

B C

F

D

Sizes 012 - 016 - 020

Sizes 004 - 008 - 010

»

Ring nut

O-ring

Coil coupling

See diagram supplied with
the kit..

» ¿ ´

Advertising