42 gw, Technical data, Table i: nominal data – Carrier 42GW User Manual

Page 4: Table v: operating limits, Table vi: accessories, Table iv: material supplied

Advertising
background image

42 GW

GB - 3

E N G L I S H

Table III: Technical data of electric heaters (if installed)

IMPORTANT:
The electric heater must
always be factory installed
(mod. 42GWE/H...).
The use of other eletric
heaters is absolutely
prohibited.
Failure to follow this
safety requirement
causes unit damage and
voids the warranty.

Table I: Nominal data

• The power cable to the electrical heaters must be type H07 RN-F.
• The unit power cable must be type H07 RN-F.

Table II: Wire section of connecting cable mm

2

*

Not to be used on units equipped with electric heater (mod.42GWE)

Table V: Operating limits

Water circuit

Water- side maximum pressure

Minimum entering water temperature: + 4

°

C

1400 kPa (142 m w.c.)

Maximum entering water temperature: + 80

°

C

Room air

Minimum temperature: 5

°

C (1)

Maximum temperature 32

°

C

Power supply

Nominal single phase voltage

230V

~

50Hz

60Hz Special Export Market

Operating voltage limits

min. 198V – max. 264V

min. 187V – max. 253V

Nominal three phase voltage

400V 3N

~

50Hz

Operating voltage limits

min. 342V – max. 462V

Notes: (1) If the room temperature can go down to 0

°

C, it is advisable to empty the water circuit to avoid damage caused by ice (see paragraph

on water connections).

Models

L/R

N/C

from 004 to 020

1.0

1.0

Note: 230V ~ 50Hz.

Description

Size / Code

004-008-010

012-016-020

2-pipe valve

42GW9003

42GW9007

4-pipe valve

42GW9004

42GW9008

Primary air

42GW9005

42GW9006

Air disch. closing

*

40GK-900---003-40

40GK-900---013-40

Active carbon filter

40GK-900---002-40

40GK-900---012-40

Electrostatic filter

40GK-900---001-40

40GK-900---011-40

Drain pan

42GW9009

42GW9010

Table VI: Accessories

Description

Size / Code

004-008-010-012-016-020

Water discharge pump

40GKX9001

Control

42GW9014

Control

42GW9015

Control

42GW9016

Control

42GW9017

Control CRC

33DFS-RM

Auxiliary board

42GW9013

Description

Q.ty

Use

Installation instructions

1

Unit installation

Fresh air intake baffle

1

Air renewal

Table IV:
Material supplied

Technical data

POWER INPUT

Models

Cooling

Heating

W

A

W

A

42GWC004

42GWC004H

66

0.28

56

0.24

42GWC008

42GWC008H

78

0.34

68

0.29

42GWC010

42GWC010H

100

0.43

90

0.39

42GWC012

42GWC012H

97

0.42

87

0.38

42GWC016

42GWC016H

135

0.58

125

0.54

42GWC020

42GWC020H

197

0.85

187

0.81

42GWD004

42GWD004H

66

0.28

56

0.24

42GWD010

42GWD010H

100

0.43

90

0.39

42GWD020

42GWD020H

197

0.85

187

0.81

POWER INPUT

Models

Cooling

Heating

W

A

W

A

42GWE004

70

0.30

1560

6.8

42GWH004

70

0.30

560

2.4

42GWE008

65

0.28

2555 11.1

42GWH008

65

0.28

555

2.4

42GWE010

94

0.40

2584 11.2

42GWE012

123

0.53

3113 13.5

42GWE016

141

0.61

3131 13.6

42GWE020

233

1.00

3223 14.0

42GWE004H

70

0.30

1560

6.8

42GWE008H

65

0.28

2555 11.1

42GWE010H

94

0.40

2584 11.2

42GWE012H

123

0.53

3113 13.5

42GWE016H

141

0.61

3131 13.6

42GWE020H

233

1.00

3223 14.0

Mod.

004

H004

008

H008

010

012

016

020

Electric heater capacity

kW

1.5

0.5

1.5+1.0 0.25+0.25 1.5+1.0

2x1 + 2x0.5

Supply voltage (ph) V 230 (1 ph) 230 (1 ph) 230 (*) 230 (1 ph) 230 (*) 400 400 400

Max. power input

A

6.50

2.1

10.8

2.1

10.8

7.5

7.5

7.5

Safety thermostat

N

°

1 Thermostat with automatic reset ST1 60

°

C

N

°

1 Thermostat with manual reset(electric) ST2 100

°

C

Power supply cables

mm

2

3 x 1.5

3 x 1.5

3 x 2.5

3 x 2.5

3 x 2.5

5 x 1.5

5 x 1.5

5 x 1.5

Recommended fuse (Type gL)

A

8

8

12

12

12

10

10

10

(*) In areas with a 2 kW limit for single-phase electric heaters it is possible to divide the power supply on two phases and

neutral of a three phase supply with neutral.
Use cable type HO7 RN-F - 4 x 1.5 mm

2

- 400V 2N~