A01222

LEGEND

24 VOLT FACTORY WIRING

24 VOLT FIELD WIRING

FIELD SPLICE CONNECTION

RELAY SPDT, PILOT DUTY
24-V COIL (HN61KK324)
OR EQUIVALENT

HUMIDISTAT, OPENS ON
HUMIDITY RISE (HL38MG026)

AIRFLOW SELECTOR

R1

H

AFS

WIRING DIAGRAM NOTES:

1. WIRING MUST CONFORM TO NEC OR LOCAL CODES.

2. UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE. FOR EXAMPLE: O/W2 MEANS O IS ENERGIZED

IN COOLING MODE.

3. REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEATURES AND WIRING INFORMA-

TION.

4. NON-PROGRAMMABLE MODEL 2S01–B, WHEN USED IN AIR CONDITIONING INSTALLATION THE R19 JUMPER MUST BE

CUT AND REMOVED.

5. PROGRAMMABLE MODEL 2S01–B MUST HAVE DIP SWITCH C ON WHEN USED IN AIR CONDITIONER APPLICATIONS.

6. THERMIDISTAT DIP SWITCH NO. 1 SHOULD BE SET IN OFF POSITION FOR AIR CONDITIONER APPLICATIONS

(FACTORY DEFAULT).

7. AS AN OPTION O/W2CAN CONTROL SECOND-STAGE HEAT.

8. THERMIDISTAT DIP SWITCH NO. 2 SHOULD BE SET IN THE ON POSITION FOR DUAL CAPACITY COMPRESSOR

OPERATION.

9. TO ACTIVATE DEHUMIDIFY FUNCTION ON FK4 OR FV4, REMOVE J1 JUMPER AT FAN COIL CONTROL BOARD.

10. AS AN OPTION, LOCK FURNACE INTO LOW-FIRE OPERATION AND LET O/W2 CONTROL HIGH FIRE OPERATION. REFER

TO FURNACE INSTALLATION INSTRUCTIONS FOR PROPER SETUP.

11. TO ACTIVATE DEHUMIDIFY FEATURE ON CURRENT STYLE, VARIABLE-SPEED, 80 PERCENT NON-CONDENSING,

FURNACE DISCONNECT GREEN (DEHUM) WIRE FROM G ON FURNACE CONTROL BOARD AND CONNECT TO
DEHUMIDIFY TERMINAL DHUM ON THERMIDISTAT.

12. THE DE JUMPERS MUST BE REMOVED TO ENABLE THE DEHUMIDIFICATION FEATURE ON FURNACE.

Table 2—Accessory Usage

ACCESSORY

REQUIRED FOR

LONG-LINE

APPLICATIONS

*

(50-175 FT.)

REQUIRED FOR

SEACOAST

APPLICATIONS

(WITHIN 2 MILES)

Coastal Filter

No

Yes

Support Feet

No

Recommended

Puron® Balance-Port Hard

Shut-off TXV

Yes†

Yes†

* For tubing line sets between 50 and 175 ft horizontal or 20 ft vertical differential, refer to Application Guideline and Service Manual—Air Conditioners and Heat Pumps
Using Puron® Refrigerant. Crankcase heater and start assist are standard on two-speed units.
† Required for all applications.