Configuration, Test mode, Fault mode – KMC Controls SAE-1162 User Manual

Page 4: Recal (recalibration) mode, Configuration 4, Warning

Advertising
background image

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors

4

Installation Guide

switch on the front cover (or activate the remote

TEST input) when the CO level is below the alarm

level (minus the hysteresis/deadband).
The Manual Reset also applies to the buzzer alarm. If

the buzzer alarm is active, pressing the TEST switch

will temporarily silence the buzzer. But to reset the

buzzer alarm to the Normal Mode, the CO level

must have dropped below the value of the trip level

(minus the hysteresis/deadband) when the TEST

switch is pressed.

Test Mode

The Test function allows verification of the output

and relay operation, and the Test time duration can

be programmed via the menu. The Test mode func-

tion is disabled by default and must be enabled via

the menu to later operate while in Normal mode.

Test mode can only be activated while the device is

in Normal mode (not if the device is in Fault, Alarm,

or ReCal modes).
To initiate the Test function (if enabled) during Nor-

mal mode, either press and hold the TEST button for

1 second or activate it remotely by shorting the TEST

+ to TEST – (COM). This will cause the Status LED to

blink red, the analog output to go to 100%, and both

relays (if installed) to activate. The buzzer will also

beep once every 15 seconds (if enabled), and the LCD

will indicate Test mode and remaining time. The

Test function will continue for 5 minutes (default),

and then the device will reset to normal operation.

The Test function can be cancelled by pressing the

TEST button a second time.

Fault Mode

The Fault mode function is disabled by default,

and it must be enabled via the menu to operate. The

Fault function will monitor the CO sensor lifetime

and indicate when the CO sensor should be re-

placed. If the device determines that the sensor has

reached the end of its useful life and that replace-

ment is necessary, it will enter Fault mode. This will

cause the Status LED to blink red and the buzzer to

beep once every 10 minutes. The LCD display will

periodically show “Sensor Fault.” The Fault mode

can be disabled via the menu or enabled at any time.

If enabled, and the device is in Fault mode, press-

ing the TEST button will “silence” the buzzer due to

the Fault alarm only. Buzzer silence due to the Fault

alarm will hold until the fault condition is reset via

the menu. (The buzzer may still activate due to a CO

setpoint alarm if enabled.)

Configuration

WARNING

All commercial CO sensors have a finite life. The
life expectancy of these models is 5 to 7 years. They
must be replaced periodically to ensure reliable
operation in detecting conditions that are potentially
hazardous to human health and safety.

ReCal (Recalibration) Mode

The ReCal mode function is enabled by default and

must be disabled via the menu if it is not required.

The ReCal function will monitor the device and in-

dicate when the CO sensor should be recalibrated. If

the device determines that the sensor requires recali-

bration, it will enter ReCal mode. This will cause the

Status LED to blink red and the buzzer to beep once

every 10 minutes. The LCD will periodically show

“ReCal Required.” If enabled, and the device is in

ReCal mode, pressing the TEST button will silence

the buzzer due to the ReCal alarm only. Buzzer

silence due to the ReCal alarm will hold until the Re-

Cal condition is reset via the menu. (The buzzer may

still activate due to a CO setpoint alarm if enabled.)

Operation parameters default to typical values but

can be configured locally via the user menu using

the LCD display and the three push-buttons on the

circuit board. Any changes made are saved in non-

volatile memory and are restored in case of a power

loss. Only the menu items relevant to the device

model and selections will be shown.
The menu can be accessed at any time after the

warm-up mode. If there is 5 minutes of inactivity the

menu will close and normal operation will continue.

The TEST button has no effect when the menu is in

use.
Menu item values are controlled by using the three

buttons on the circuit board (ROLL, MENU, and

SAVE). To enter the menu, press and release the

<MENU> key. This will enter the menu Step 1, and

pressing the <MENU> key a second time advances to

Step 2. Each press of the <MENU> key advances the

menu item. No values are saved or changed by using

the <MENU> key.
The <ROLL> key is used to make changes to

program values by scrolling through the available

options. Holding the <ROLL> key pressed will scroll

through some options at a faster rate.

Advertising
This manual is related to the following products: