background image

Residential Wattage Requirements

Appliance

Running

Watts

Add watts

for starting

Furnace blower, gas or fuel

1/8 hp

300

500

1/8 hp

500

750

1/6 hp

500

750

1/4 hp

600

1000

1/3 hp

700

1400

1/2 hp

875

2100

Shallow well pump

1/3 hp

750

1400

1/2 hp

1000

2350

Sump pump

1/3 hp

800

1300

1/2 hp

1050

2150

Refrigerator or freezer

800

2300

Garage door opener

1/4 hp

550

1100

1/3 hp

750

1400

Lights on

bulb

0

Radio 50-200

0

Television 100-300

0

Microwave oven

600-1500

0

Coffee maker, typical

1750

0

Toaster/toaster oven

1050-1850

0

Portable heater

1100-1500

0

Dehumidifier 650-800

0

Electric blanket

400

0

Clothes washer

1150

2300

Clothes dryer, gas

700

1800

Dishwasher

cool dry

700

1400

hot dry

1450

1400

Vacuum cleaner

800-1100

0

Hair dryer

300-1500

0

Iron 1200

0

1