Reliance Controls Pro/Tran Q Series User Manual

Page 8

Advertising
background image



















Installing 240-volt Circuits

Any two adjacent circuit selector switches may be used for a double-pole 240-volt circuit.
Use a handle tie to connect the two circuit selector switches.

*Note: Circuits used for multi-wire branch circuits are not available for 240-volt

circuits

Removing handle ties. If there are no 240-volt or multi-wire circuits in the transfer switch
installation, handle-ties on the switches are not needed. To remove a handle tie, place the
handle-tied switch in the GEN position. Loosen the two screws and remove the handle tie.
Adding handle ties. If additional ties are needed to accommodate additional 240-volt
or multi-wire circuits, they can be added to adjacent pairs of switches.

6


Warning: Transfer switch circuits with 20 amp breakers must be installed on only
those branch circuits with 20 amp branch circuit breakers. Transfer switch circuits
with 15 amp breakers can be installed on 15 or 20 amp branch circuits. Do not
install any transfer switch circuit on branch circuits greater than 20 amps,
except in position A and B which maybe 30 amps.




Installing 240-volt circuit(s)

1. Locate the two red and two black wires from any adjacent circuit positions.

2. Turn off the double-pole breaker in the load center.

Advertising