3. Loosen the screws that secure each wire to each circuit breaker. Disconnect the wires

from the circuit breakers.

4. Feed the two red wires in Step 1 to the double-pole circuit breaker.

5. Cut the red wires to a convenient length. Strip 5/8" from the end of each wire. Connect

the two red wires to the double-pole circuit breaker.

6. Cut the black wires to a length convenient for aligning with wires removed from the

circuit breaker. Strip 5/8" from the end of each wire.

7. Insert one wire removed from the circuit breaker and one black wire into a yellow wire

connector. Twist to tighten and push the wires back into the wiring compartment of the
load center. Do the same for the other wire removed from the circuit breaker and the
other black wire from the transfer switch.

8. Be sure that a handle tie is connected between the two circuit selector switches.

Repeat steps 1-8 for the other double-pole circuits.

30-Ampere Circuits. Only circuits A and B may be used for 30-amp. circuits. Follow the
above wiring instructions for installing 240-volt circuits. If 30-amp. single-pole circuits are
being used, refer to the previous section regarding installation of 120-volt cirucits.

For models with -C or -D suffix, or to hard wire any cord-connected model, continue to the
next section entitled "Hard-wire Installation" to complete the installation.

For all other models, skip to "Completing the installation" on page 8.

Hard-wire Installation

"Hard-wire" installation to a power inlet box located remotely from the transfer switch (Figure
6)
requires additional steps to complete the installation. The wire connections to the wires
from power inlet box are made in the wiring compartment of the transfer switch. Access the
wiring compartment by removing the two screws located on the sides of the lower wiring
compartment cover. Replace when installation is complete. For models with wattmeters, see
wattmeter sections below before making the
following connections.

For models having a terminal block in the wiring
compartment, connect to the remote power inlet
box as follows:
From the transfer switch, connect:

ƒ the black terminal to the power inlet X or Y

terminal

ƒ the white terminal to the power inlet neutral W

terminal

ƒ the red terminal to the power inlet X or Y

terminal

ƒ

the green terminal to the power inlet ground G
terminal.