VSUB INDUCER OR COMBUSTION AIR BLOWER INTERLOCK WITH VFD

VSUB DRAFT INDUCER INTERLOCK WITH VFD

230 VOLT VSUB DRAFT INDUCER WIRING

460 VOLT VSUB DRAFT INDUCER WIRING

RED

ORANGE

BLUE

GREEN

BLACK

BLACK

BLACK

VSUB BLOWER

TSTAT

MOTOR HEATER

GROUND

MOTOR LIMIT

MOTOR

Max. length:

dedicated metal conduit.

Wiring is to be in

230 VAC SUPPLY / LOAD WIRING

LEGEND:

LOW VOLTAGE / DC CONTROL WIRING

300' (91m) @ 230 VAC

TJERNLUND DRIVE MODEL

VFD- _ _ _ _ _ _ _ 2C3

"2" means "230 VAC"

VFD

CONTROL

BOX

M1

M2

M3

MG

ND

S1

S2

F1

F2

GN

D

L1

L2/

N

L3

NC

NC

L

L

MB

MC

M1

M2

S1

S2

SC

S3

D-

D+

plate rating before applying power. Improper supply voltage

Verify that the input power voltage matches the VFD's name-

All wiring must be in metal conduit (best) or shielded cable.

the same conduit. Undesired VFD operation could result.

Do not run the VFD's input power and output power wiring in

Verify that the blower (VSUB 8/12/16/20) is wired for the
output voltage from the VFD. If not correct, severe damage to

3.

2.

1.

3.

2.

WARNINGS:

CAUTIONS:

1.

to the VFD could damage the VFD.

the blower and/or the VFD could result.

When the system is completely installed, perform the safety
interlock and operational test as outlined in the installation

4.

manuals. Failure to do these tests could result in an unsafe
and/or incorrectly operating system.

"C" means "Closed Loop"

"3" means "CPC-3 Control"

3

3

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

GRAY

WHT/BRN

VFD COMMUNICATIONS CABLE

& 30 WATTS FOR VSUB20)

ARCTIC-DUTY

MOTOR HEATER

(15 WATTS FOR VSUB8,12,16

RED

WINDINGS

MOTOR

2

A

DD F

O

R 208-230 V

A

C 3Ø

208-230 V

A

C 1Ø /

60 HZ

4 x 4 WEATHERPROOF

BOX AND WHIP

2

This blower is shipped from the factory wired for 460 VAC.

4.

Reconfigure the motor wiring at the motor for 230 VAC.
See the Motor Label for details.

4

Route transducer wiring in metal conduit or use Belden Shield
Cable #9939 or equivalent. Make sure the transducer wiring
does not contain or cross line voltage wiring or undesired

Use caution to ensure that the wiring to the transducer is

Improper wiring to the transducer will destroy the transducer.

correct before activating the CPC-3 controller.

transducer performance may result.

INCLUDED CABLE

NOTES:

If the provided 10-foot, 10-wire VFD control cable is not long

1.

enough to meet the application needs, use caution to ensure
that the connections from the VFD to the CPC-3 controller
are correctly located. MB to MB, MC to MC, etc. In addition,

Use caulking to seal the electrical box cover to the electrical

2.

box, and to seal the conduit holes to hole plugs.

reference the Wire Length Table.

If required, non-fused disconnects are to be supplied by the

3.

installer.

3

FIGURE 8052019 11/18/04

460 VAC SUPPLY / LOAD WIRING

plate rating before applying power. Improper supply voltage

Verify that the input power voltage matches the VFD's name-

All wiring must be in metal conduit (best) or shielded cable.

the same conduit. Undesired VFD operation could result.

Do not run the VFD's input power and output power wiring in

Verify that the blower (VSUB 8/12/16/20) is wired for the
output voltage from the VFD. If not correct, severe damage to

3.

2.

1.

3.

2.

WARNINGS:

CAUTIONS:

1.

to the VFD could damage the VFD.

the blower and/or the VFD could result.

When the system is completely installed, perform the safety
interlock and operational test as outlined in the installation

4.

manuals. Failure to do these tests could result in an unsafe
and/or incorrectly operating system.

NOTES:

If the provided 10-foot, 10-wire VFD control cable is not long

1.

enough to meet the application needs, use caution to ensure
that the connections from the VFD to the CPC-3 controller
are correctly located. MB to MB, MC to MC, etc. In addition,

"C" means "Closed Loop"

"3" means "CPC-3 Control"

460 VAC / 3Ø / 60 HZ

3

RED

ORANGE

BLUE

GREEN

BLACK

BLACK

BLACK

VSUB BLOWER

TSTAT

MOTOR HEATER

GROUND

MOTOR LIMIT

4 x 4 WEATHERPROOF

BOX AND WHIP

MOTOR

Max. length:

dedicated metal conduit.

Wiring is to be in

230 VAC SUPPLY / LOAD WIRING

LEGEND:

LOW VOLTAGE / DC CONTROL WIRING

100' (30m) @ 460 VAC

TJERNLUND DRIVE MODEL

VFD- _ _ _ _ _ _ _ 4C3

"4" means "460 VAC"

2

VFD

CONTROL

BOX

M1

M2

M3

MG

ND

S1

S2

F1

F2

GN

D

L1

L2/

N

L3

NC

NC

L

L

MB

MC

M1

M2

S1

S2

SC

S3

D-

D+

3

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

GRAY

WHT/BRN

Use caulking to seal the electrical box cover to the electrical

2.

box, and to seal the conduit holes to hole plugs.

2

VFD COMMUNICATIONS CABLE

reference the Wire Length Table.

& 30 WATTS FOR VSUB20)

ARCTIC-DUTY

MOTOR HEATER

(15 WATTS FOR VSUB8,12,16

RED

WINDINGS

MOTOR

Route transducer wiring in metal conduit or use Belden Shield
Cable #9939 or equivalent. Make sure the transducer wiring
does not contain or cross line voltage wiring or undesired

Use caution to ensure that the wiring to the transducer is

Improper wiring to the transducer will destroy the transducer.

correct before activating the CPC-3 controller.

transducer performance may result.

INCLUDED CABLE

If required, non-fused disconnects are to be supplied by the

3.

installer.

3

FIGURE 8052018 11/18/04

230 VOLT VSUB COMBUSTION AIR BLOWER WIRING

460 VOLT VSUB COMBUSTION AIR BLOWER WIRING

plate rating before applying power. Improper supply voltage

Verify that the input power voltage matches the VFD's name-

All wiring must be in metal conduit (best) or shielded cable.

the same conduit. Undesired VFD operation could result.

Do not run the VFD's input power and output power wiring in

Verify that the blower (VSUB 8/12/16/20) is wired for the
output voltage from the VFD. If not correct, severe damage to

3.

2.

1.

3.

2.

WARNINGS:

CAUTIONS:

1.

to the VFD could damage the VFD.

the blower and/or the VFD could result.

When the system is completely installed, perform the safety
interlock and operational test as outlined in the installation

4.

manuals. Failure to do these tests could result in an unsafe
and/or incorrectly operating system.

NOTES:

If the provided 10-foot, 10-wire VFD control cable is not long

1.

enough to meet the application needs, use caution to ensure
that the connections from the VFD to the CPC-3 controller
are correctly located. MB to MB, MC to MC, etc. In addition,

"C" means "Closed Loop"

"3" means "CPC-3 Control"

3

3

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

GRAY

WHT/BRN

RED

ORANGE

BLUE

GREEN

BLACK

BLACK

BLACK

VSUB BLOWER

TSTAT

MOTOR HEATER

GROUND

MOTOR LIMIT

4 x 4 WEATHERPROOF

BOX AND WHIP

FFP-1

Max. length:

dedicated metal conduit.

Wiring is to be in

230 VAC SUPPLY / LOAD WIRING

LEGEND:

LOW VOLTAGE / DC CONTROL WIRING

300' (91m) @ 230 VAC

TJERNLUND DRIVE MODEL

VFD- _ _ _ _ _ _ _ 2C3

"2" means "230 VAC"

VFD

CONTROL

BOX

M1

M2

M3

MG

ND

S1

S2

F1

F2

GN

D

L1

L2/

N

L3

NC

NC

L

L

MB

MC

M1

M2

S1

S2

SC

S3

D-

D+

Use caulking to seal the electrical box cover to the electrical

2.

box, and to seal the conduit holes to hole plugs.

2

VFD COMMUNICATIONS CABLE

reference the Wire Length Table.

& 30 WATTS FOR VSUB20)

ARCTIC-DUTY

MOTOR HEATER

(15 WATTS FOR VSUB8,12,16

RED

WINDINGS

MOTOR

Route transducer wiring in metal conduit or use Belden Shield
Cable #9939 or equivalent. Make sure the transducer wiring
does not contain or cross line voltage wiring or undesired

Use caution to ensure that the wiring to the transducer is

Improper wiring to the transducer will destroy the transducer.

correct before activating the CPC-3 controller.

transducer performance may result.

The FFP-1 will disable the combustion air blower when

5.

excessively hot or cold room air is detected. Refer to the
FFP-1 installation instructions for details.

REFER TO FFP-1 INSTALLATION

INSTRUCTIONS FOR DETAILS

HEAT LIMIT

FREEZE LIMIT

5

This blower is shipped from the factory wired for 460 VAC.

4.

Reconfigure the motor wiring at the motor for 230 VAC.
See the Motor Label for details.

2

A

DD F

O

R

208-230 V

A

C

MOTOR

4

INCLUDED CABLE

3

FIGURE 8052021 11/18/04

8052021 S

H

E

E

T

2

If required, non-fused disconnects are to be supplied by the

3.

installer.

208-230 V

A

C 3Ш

1Ш /

60 HZ

460 VAC SUPPLY / LOAD WIRING

plate rating before applying power. Improper supply voltage

Verify that the input power voltage matches the VFD's name-

All wiring must be in metal conduit (best) or shielded cable.

the same conduit. Undesired VFD operation could result.

Do not run the VFD's input power and output power wiring in

Verify that the blower (VSUB 8/12/16/20) is wired for the
output voltage from the VFD. If not correct, severe damage to

3.

2.

1.

3.

2.

WARNINGS:

CAUTIONS:

1.

to the VFD could damage the VFD.

the blower and/or the VFD could result.

When the system is completely installed, perform the safety
interlock and operational test as outlined in the installation

4.

manuals. Failure to do these tests could result in an unsafe
and/or incorrectly operating system.

NOTES:

If the provided 10-foot, 10-wire VFD control cable is not long

1.

enough to meet the application needs, use caution to ensure
that the connections from the VFD to the CPC-3 controller
are correctly located. MB to MB, MC to MC, etc. In addition,

"C" means "Closed Loop"

"3" means "CPC-3 Control"

460 VAC / 3Ø / 60 HZ

3

230 VAC SUPPLY / LOAD WIRING

LEGEND:

LOW VOLTAGE / DC CONTROL WIRING

100' (30m) @ 460 VAC

TJERNLUND DRIVE MODEL

VFD- _ _ _ _ _ _ _ 4C3

"4" means "460 VAC"

2

VFD

CONTROL

BOX

M1

M2

M3

MG

ND

S1

S2

F1

F2

GN

D

L1

L2/

N

L3

NC

NC

L

L

MB

MC

M1

M2

S1

S2

SC

S3

D-

D+

3

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

GRAY

WHT/BRN

Use caulking to seal the electrical box cover to the electrical

2.

box, and to seal the conduit holes to hole plugs.

2

VFD COMMUNICATIONS CABLE

reference the Wire Length Table.

& 30 WATTS FOR VSUB20)

ARCTIC-DUTY

MOTOR HEATER

(15 WATTS FOR VSUB8,12,16

RED

WINDINGS

MOTOR

Route transducer wiring in metal conduit or use Belden Shield
Cable #9939 or equivalent. Make sure the transducer wiring
does not contain or cross line voltage wiring or undesired

Use caution to ensure that the wiring to the transducer is

Improper wiring to the transducer will destroy the transducer.

correct before activating the CPC-3 controller.

transducer performance may result.

The FFP-1 will disable the combustion air blower when

4.

excessively hot or cold room air is detected. Refer to the
FFP-1 installation instructions for details.

REFER TO FFP-1 INSTALLATION

INSTRUCTIONS FOR DETAILS

HEAT LIMIT

FREEZE LIMIT

4

MOTOR

INCLUDED CABLE

If required, non-fused disconnects are to be supplied by the

3.

installer.

3

FIGURE 8052020 11/18/04

RED

ORANGE

BLUE

GREEN

BLACK

BLACK

BLACK

VSUB BLOWER

TSTAT

MOTOR HEATER

GROUND

MOTOR LIMIT

4 x 4 WEATHERPROOF

BOX AND WHIP

FFP-1

Max. length:

dedicated metal conduit.

Wiring is to be in

Advertising