Max. vfd to cpc-3 lead length – Tjernlund CPC-3 Constant Pressure Controller Startup Manual 8504125 User Manual

Page 9

Advertising
background image

8

230 VOLT VSAD SERIES WIRING

460 VOLT VSAD SERIES WIRING

plate rating before applying power. Improper supply voltage

Verify that the input power voltage matches the VFD's name-

All wiring must be in metal conduit (best) or shielded cable.

the same conduit. Undesired VFD operation could result.

Do not run the VFD's input power and output power wiring in

Verify that the venter (VSAD 8/10/12-230) is rated for the
output voltage from the VFD. If not correct, severe damage to

3.

2.

1.

3.

2.

WARNINGS:

CAUTIONS:

1.

to the VFD could damage the VFD.

the venter and/or the VFD could result.

When the system is completely installed, perform the safety
interlock and operational test as outlined in the installation

4.

manuals. Failure to do these tests could result in an unsafe
and/or incorrectly operating system.

NOTES:

"C" means "Closed Loop"

"3" means "CPC-3 Control"

3

3

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

GRAY

WHT/BRN

VFD COMMUNICATIONS CABLE

A

DD F

O

R 208-230 V

A

C 3Ø

208-230 V

A

C 1Ø /

60 HZ

Route transducer wiring in metal conduit or use Belden Shield
Cable #9939 or equivalent. Make sure the transducer wiring
does not contain or cross line voltage wiring or undesired

Use caution to ensure that the wiring to the transducer is

Improper wiring to the transducer will destroy the transducer.

correct before activating the CPC-3 controller.

transducer performance may result.

4

For vertical termination of the VSAD venter, connect the S2
position to the orange wire and cap off the gray wire as shown.

For horizontal termination of the VSAD venter, connect the S2
position to the gray wire and cap off the orange wire.

4.

If the provided 10-foot, 10-wire VFD control cable is not long

1.

enough to meet the application needs, use caution to ensure
that the connections from the VFD to the CPC-3 controller
are correctly located. MB to MB, MC to MC, etc. In addition,

Use caulking to seal the electrical box cover to the electrical

2.

box, and to seal the conduit holes to hole plugs.

2

reference the Wire Length Table.

If required, non-fused disconnects are to be supplied by the

3.

installer.

3

FIGURE 8052017 11/18/04

INCLUDED

39" (1m) CABLE

BLACK

BLACK

ORANGE

BLUE

GREEN

VIOLET

RED

YELLOW

VSAD MOTOR ENCLOSURE

COOLING FAN

THERMOSTAT

FAN

GND

VERTICAL

TILT SWITCH

MOTOR

LIMIT

HIGH
LIMIT

L3

L2

L1

GRAY

BLK

BLK

BLK

BLK

BLK

BLUE

BLUE

WHT/BRN

HORIZONTAL

TILT SWITCH

BLK

WEATHERPROOF

BOX AND WHIP

MOTOR

Max. length:

dedicated metal conduit.

Wiring is to be in

230 VAC SUPPLY / LOAD WIRING

LEGEND:

LOW VOLTAGE / DC CONTROL WIRING

300' (91m) @ 230 VAC

TJERNLUND DRIVE MODEL

VFD- _ _ _ _ _ _ _ 2C3

"2" means "230 VAC"

2

VFD

CONTROL

BOX

M1

M2

M3

MG

ND

S1

S2

F1

F2

GN

D

L1

L2/

N

L3

NC

NC

L

L

MB

MC

M1

M2

S1

S2

SC

S3

D-

D+

INCLUDED

39" (1m) CABLE

BLACK

BLACK

ORANGE

BLUE

GREEN

VIOLET

RED

YELLOW

VSAD MOTOR ENCLOSURE

COOLING FAN

THERMOSTAT

FAN

GND

VERTICAL

TILT SWITCH

MOTOR

LIMIT

HIGH
LIMIT

L3

L2

L1

GRAY

BLK

BLK

BLK

BLK

BLK

BLUE

BLUE

WHT/BRN

HORIZONTAL

TILT SWITCH

BLK

WEATHERPROOF

BOX AND WHIP

MOTOR

Max. length:

dedicated metal conduit.

Wiring is to be in

230 VAC SUPPLY / LOAD WIRING

LEGEND:

LOW VOLTAGE / DC CONTROL WIRING

100' (30m) @ 460 VAC

TJERNLUND DRIVE MODEL

VFD- _ _ _ _ _ _ _ 4C3

"4" means "460 VAC"

2

4

VFD

CONTROL

BOX

M1

M2

M3

MG

ND

S1

S2

F1

F2

GN

D

L1

L2/

N

L3

NC

NC

L

L

MB

MC

M1

M2

S1

S2

SC

S3

D-

D+

460 VAC SUPPLY / LOAD WIRING

plate rating before applying power. Improper supply voltage

Verify that the input power voltage matches the VFD's name-

All wiring must be in metal conduit (best) or shielded cable.

Route transducer wiring in metal conduit or use Belden Shield

the same conduit. Undesired VFD operation could result.

Do not run the VFD's input power and output power wiring in

Verify that the venter (VSAD 8/10/12-460A) is rated for the
output voltage from the VFD. If not correct, severe damage to

3.

2.

1.

3.

2.

WARNINGS:

Cable #9939 or equivalent. Make sure the transducer wiring

CAUTIONS:

does not contain or cross line voltage wiring or undesired

Use caution to ensure that the wiring to the transducer is

Improper wiring to the transducer will destroy the transducer.

1.

correct before activating the CPC-3 controller.

to the VFD could damage the VFD.

the venter and/or the VFD could result.

When the system is completely installed, perform the safety
interlock and operational test as outlined in the installation

4.

manuals. Failure to do these tests could result in an unsafe
and/or incorrectly operating system.

For vertical termination of the VSAD venter, connect the S2
position to the orange wire and cap off the gray wire as shown.

For horizontal termination of the VSAD venter, connect the S2
position to the gray wire and cap off the orange wire.

4.

NOTES:

If the provided 10-foot, 10-wire VFD control cable is not long

1.

enough to meet the application needs, use caution to ensure
that the connections from the VFD to the CPC-3 controller
are correctly located. MB to MB, MC to MC, etc. In addition,

"C" means "Closed Loop"

"3" means "CPC-3 Control"

460 VAC / 3Ø / 60 HZ

3

3

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

GRAY

WHT/BRN

transducer performance may result.

Use caulking to seal the electrical box cover to the electrical

2.

box, and to seal the conduit holes to hole plugs.

2

VFD COMMUNICATIONS CABLE

reference the Wire Length Table.

If required, non-fused disconnects are to be supplied by the

3.

installer.

3

FIGURE 8052016 11/18/04

VSAD DRAFT INDUCER INTERLOCK WITH VFD

VFD & INDUCER / C.A. BLOWER WIRING

WARNINGS:
1. Verify that the input power voltage matches the VFD's nameplate rating before applying power. Incorrect supply voltage can

damage VFD.

2. Verify that the Inducer/Blower is rated for the same voltage as the VFD. Incorrect voltage can damage motor and VFD.

3. Maximum wire lengths between the VFD and the inducer/blower are:

230 VAC Models: 300 feet with 14 AWG, 600 VAC Insulation
460 VAC Models: 100 feet with 14 AWG, 600 VAC insulation

CAUTIONS:
1. All wiring must be in metal conduit.
2. Do not route the VFD's input and output wiring in the same conduit. Undesired system operational effects could occur.

NOTES:
1. If the provided 10-foot, 10-wire VFD control cable is not long enough, use caution to ensure that the wires from

the VFD control cable are correctly extended. Route in metal conduit. All connections between the VFD and the
CPC-3 must alpha/numerically match.MB to MB, MC to MC, etc. See maximum lead length chart to right.

2. Use caulk to seal the exterior electrical box cover and to seal any conduit hole plugs.

3. If required, use only non-fused disconnects.

4. Wire proper Vertical or Horizontal Tilt Switch on VSAD-Series Inducers. For vertical termination of VSAD-Series inducers, connect

the S2 position to the Orange wire and cap off the Grey wire. For horizontal terminations of VSAD-Series inducers, connect the S2
position to the Grey wire and cap off the Orange wire.

5. VSUB-Series Blowers are shipped from the factory internally wired for 460 VAC. For 230 VAC applications reconfigure the motor’s

internal wiring for 230 VAC by following the diagram on motor label.

6. VSUB-Series Blowers used to provide combustion air must install the FFP-1. The FFP-1 will disable the C. A. Blower when exces-

sively hot or cold temperatures are detected in the mechanical room. Refer to FFP-1 instructions for details.

Wire Gage

Max. Distance

600' (183m)

14 AWG

390' (119m)
220' (67m)

16 AWG
18 AWG

22 AWG

20 AWG

110' (34m)

165' (50m)

900' (274m)

12 AWG

Max. VFD to CPC-3

Lead Length