Cpc-3 control – Tjernlund CPC-3 Constant Pressure Controller Startup Manual 8504125 User Manual

Page 7

Advertising
background image

6

Positions P1 & P2 are for the PSA-1, manual mode proving switch. Position P1 outputs a 5 VDC signal to the PSA-1 Proving
Switch. When the switch closes it returns the signal to position P2, allowing interlocked heaters to operate with the CPC-3 in
Manual Mode.

Positions G, R & B connect to a TD-Series transducer. Position G receives the 1-10 VDC output from the transducer. Position R is
the 24 VDC power supply to the transducer. Position B is the ground for the transducer.

Positions D+ & D- connect to the VFD through the included communications cable. Position D+ outputs a 1-10 VDC signal to the
VFD to modulate the inducer/blower. Position D- is the reference ground.

Positions S3, SC, S2 and S1 connect to the VFD through the included communications cable. These connections enable reset of
a faulted VFD and reverse the rotation of an inducer/blower from the CPC-3 controller.

Positions M1, M2, MC and MB connect to the VFD through the included communications cable. Position M1 outputs a 5 VDC sig-
nal to the inducer/blower limit circuits. This signal must return to position M2 or a mechanical fault will be posted on the display
and the Limit Status OK LED will not be lit. Position MC outputs a 5 VDC signal to a N/C fault relay within the VFD. This signal
must return to position MB or a VFD fault will be noted in the display and the VFD Status OK Green LED will not be lit.

G1 & H1) Inducer / C.A. Blower Rotation Selectors:

Below the Inducer (Draft) and Combustion Air terminal strips are two sets of dip switches. These dip switches determine the
rotation of the inducer/blower being controlled by that particular terminal strip. The two dip switches at each position must
always be switched opposite of each other or the VFD will receive simultaneous FWD/REV run commands, causing it to
fault. See "Checking Rotation", page 12.

I) CPC-3 Reset Button:

Pressing this button resets the CPC-3 controller with a "soft boot". It can be used in lieu of the power switch to "re-boot" the micro-
controllers of the CPC-3 without power spiking the board.

LOW VOLTAGE VFD CONTROL CABLE WIRING TO CPC-3

FIGURE 8055010 8/30/04

D+

D-

S3S

CS2

S1M2

M1MC

MB

B

R

G

B

R

G

S1S2

CPC-3 CONTROL

SENSORS

AUX. SENSO

R

INDUCE

R

2

1

B

R

G

P1

P2

SELECTOR

INDUCER

MOTOR

ROTATION

from the Inducer VFD to the CPC-3 Inducer terminal strip.

Be sure to route the communications cable in metal conduit

1.

NOTES:

to route each wire from the Inducer VFD to the CPC-3

If a longer communication cable is required, make sure

2.

Inducer terminal strip correctly. MB to MB, MC to MC, etc.

BLACK

VIOLET

ORANGE

GRN/YEL

BLUE

YELLOW

WHT/RED

RED

WHT/BRN

GRAY

WITH VFD

10 FOOT

COMMUNICATION

CABLE PROVIDED

NOT USED -

FOR FUTURE

DEVELOPMENT

NOT USED -

FOR FUTURE DEVELOPMENT

THE INDUCER
TERMINAL STRIP

INSERT PLUG INTO THE INDUCER

VFD RECEPTACLE

GRAY

WH

T

/B

R

N

RED

WH

T

/R

E

D

YELLO

W

GRN/YEL

BLUE

ORANGE

VIOL

ET

BLACK

TOP LEFT CORNER

CPC-3 CONTROL

BOARD

RS232

COM.

PORT

NOTE: The diagram below is suitable for both the Inducer or Combustion Air side of the the CPC-3 board. While the software that
runs draft or combustion air differs, the communication to the VFD's that control the Inducer / C.A. Blower is identical. The following
information is applicable to both the CPC-3 Inducer and Combustion Air terminal strips.

WIRING

All wiring from the Inducer / C.A. Blower to the heater must be in compliance with the local codes or in their absence, the National
Electric Code (NFPA 70).

All wiring from the Inducer/blower to the heater must be appropriate class 1 wiring installed in rigid metal conduit or intermediate metal
conduit. This installation manual does not contain any system design documentation. Installation and use of Tjernlund controls like the
EXP-4E Heater Interlock Expansion boards or VFD-Series Variable Frequency Drives are not covered by this manual. Please refer to
those installation manuals for details.

INDUCER OR
COMBUSTION AIR
MOTOR ROTATION
SELECTOR

NOTES:
1. Be sure to route the communications cable in metal conduit

from the Inducer or C. A. Blower to the respective CPC-3
Inducer or Combustion Air terminal strip.

2. If a longer communication cable is required, make sure to route

each wire from the Inducer or C.A. Blower VFD to the respec-
tive CPC-3 Inducer or Combustion Air terminal strip.