Attach all the remaining power supply connections to the

various peripherals as needed, these connectors are “keyed”, so

there will be only one possible way to connect them.

Before applying power to the system, make sure there are no

loose or incorrect connectors. You do not need to worry about

the setting of AC Input because of the units’ full range or auto

voltage selecting features. Double check that all connections to

the M/B are matched properly. May be you would like to test the

reduncancy function before you put back the cover of your

system chassis. Turn on (Remote on ) the on/off switch, you will

notice that if the power unit is operating properly, then

individual LEDs, external warning LEDs ( please refer to Sec.

1.11 for detail explanation) are lit Green, now remove one of the

power modules, the warning buzzer in the power system will

sound and the external warning LED which display the status of

the total power supply system will change color to be Red, the

individual LEDs (both on the rear side or on the front control

panel) indicating the power supply’s status will not light.

Meanwhile, the power supply will continue to backup the power