output without affecting the computer system’s operation.

The warning buzzer will continue sound, the user can reset the

warning buzzer by pressing the buzzer reset or use the reset

switch which all can be found on the front control panel of the

system chassis, the reset switch can be connected by wires lead

provided from the power supply system (please refer to Sec.

1.11). Insert the power module which is removed for testing

earlier, the sound of the warning buzzer will disappear, the

external warning LED will turn Green again. The LED

indicating the status of the power supply will light again, test

another power supply by performing the similar procedure.

If you use the power defective signal, there are two pins

connector (refer to Sec. 1.9), it should be connected to the

FAB-5 card properly, please refer its “User’s Manual”.

If everything works out fine, then turn off (remote off) the

power system, now put back the cover of the case and tighten

with the screws which you have retained earlier. Now you have

completed the installation of the R2U redundant power supply

system.