Series 24 Minimum Piping Recommendations – Water Boiler

Recommendation 1

is used

when the load is constant and
not varied due to mixing or
multiple zones. Use when:

system return water is not

less than 135° F for
prolonged periods of time

system flow does not impact

flow through the boiler

DRAIN VALVE

(SEE NOTE 4)

24-03 THRU 24-11 (W/20°F DROP)
24-03 THRU 24-12 (W/40°F DROP)

24-12 (W/20°F DROP)

DRAIN VALVE

(SEE NOTE 4)

REAR OF

BOILER

REAR OF

BOILER

3” x 12” NIPPLE
AND BELL REDUCER

(SEE NOTE 3)

SUPPLY

RETURN

2

RETURN

RETURN

HEADER

RETURN

BRANCH

2

2A

23 2

1

2B

1

SUPPLY

1

Recommendation 2

is a primary-secondary piping method

that maintains a constant flow through the boiler by using a
secondary boiler circulator. This arrangement isolates the
boiler from flow variations but does not safe-guard against
cold return water temperatures. Use when:

system return water is not less than 135° F

for prolonged periods of time

system flow does not impact flow through the

boiler (i.e. zoning, mixing)

BOILER CIRCULATOR

(BY OTHERS - SEE NOTE 5)

DRAIN VALVE

(SEE NOTE 4)

SUPPLY

SYSTEM PUMP

CLOSELY
SPACED

TEES

MAX

4D

BOILER CIRCULATOR

(BY OTHERS - SEE NOTE 5)

DRAIN VALVE

(SEE NOTE 4)

SUPPLY

SYSTEM PUMP

CLOSELY
SPACED

TEES

MAX

4D

D

REAR OF

BOILER

RETURN

3” x 12” NIPPLE

AND BELL REDUCER

(SEE NOTE 4)

REAR OF

BOILER

RETURN

RETURN HEADER

RETURN BRANCH

2

2

2A

2B

1

23 2

1

24-03 THRU 24-11 (W/20°F DROP)
24-03 THRU 24-12 (W/40°F DROP)

24-12 (W/20°F DROP)

RETURN PIPING SIZE (IN)

SUPPLY

RETURN

RETURN

PIPING

HEADER

BRANCH

SIZE (IN) (1)

RETURN (2)

(2A)

(QTY.) SIZE (2B)

BOILER

20°F

40°F

20°F

40°F

20°F

20°F

MODEL

DROP

DROP

DROP

DROP

DROP

DROP

24-03

2

1-1/2

2

1-1/2

24-04

2

1-1/2

2

1-1/2

24-05

2

1-1/2

2

1-1/2

24-06

2-1/2

1-1/2

2-1/2

1-1/2

24-07

2-1/2

2

2-1/2

2

24-08

2-1/2

2

2-1/2

2

24-09

3

2

3

2

24-10

3

2-1/2

3

2-1/2

24-11

3

2-1/2

3

2-1/2

24-12

4

2-1/2

4

2-1/2

3

(2) 3

Notes:
1. All piping is schedule 40.
2. Pipe sizes listed are based on a 20° F or 40°F differential (temperature drop).

Select one to match application.

3. When specified return piping is less than 3”, install 3” x 12” nipple and appropriate

size bell reducer directly into boiler return tapping as shown.

4. Drain valve—ball valve preferable, gate valve acceptable alternative

(supplied by others).—Minimum valve size per ASME code is 3/4 ” NPT.

BOILER CIRCULATOR

(BY OTHERS - SEE NOTE 5)

DRAIN VALVE

(SEE NOTE 4)

SUPPLY

SYSTEM PUMP

CLOSELY
SPACED

TEES

MAX

4D

BOILER CIRCULATOR

(BY OTHERS - SEE NOTE 5)

DRAIN VALVE

(SEE NOTE 4)

SUPPLY

SYSTEM PUMP

CLOSELY
SPACED

TEES

MAX

4D

D

REAR OF

BOILER

RETURN

3” x 12” NIPPLE

AND BELL REDUCER

(SEE NOTE 4)

REAR OF

BOILER

RETURN

RETURN HEADER

RETURN BRANCH

2

2

2A

2B

1

23 2

1

24-03 THRU 24-11 (W/20°F DROP)
24-03 THRU 24-12 (W/40°F DROP)

24-12 (W/20°F DROP)

PIPE SIZING AND NOTES FOR RECOMMENDATIONS 1 AND 2