Series 24 specifications, Beckett gas burners, Beckett oil burners – Crown Series 24 User Manual

Page 8: Commercial hot water or steam boiler, Natural gas), Available from

Advertising
background image

Series 24 Specifications

BURNER

HEATING

WATER

BOILER WEIGHT

NET I=B=R RATING

INPUT

SURFACE

NET

PRESSURE

CONTENT

w/ WATER

GROSS

(SQ. FT.)

FIREBOX

IN

(GAL.)

(LBS.)

VENT

BOILER

HORSE- OUTPUT

SQ. FT.

MBH

MBH

OIL

GAS

VOLUME FIREBOX

DIA.

MODEL

POWER

(MBH)

STEAM

STEAM

WATER

(GPH)

(MBH)

STEAM

WATER

(CU. FT.) (“W.C.”)

STEAM

WATER

STEAM

WATER

(IN.)

24-03

10.2

342

1071

257

297

3.05

438

34.2

37.0

3.2

.33

44.5

66.0

1439

1618

7

24-04

14.1

471

1471

353

410

4.10

594

48.6

54.3

4.8

.38

53.0

75.0

1811

1995

7

24-05

18.9

634

1983

476

551

5.50

792

63.0

71.5

6.4

.31

61.5

84.0

2184

2372

8

24-06

23.8

797

2492

598

693

6.90

990

77.5

88.8

7.9

.38

70.0

93.0

2557

2749

8

24-07

28.0

937

2929

703

815

8.10

1174

91.9

106.0

9.5

.36

78.5

102.0

2930

3126

8

24-08

32.5

1087

3396

815

945

9.40

1358

106.3

123.3

11.0

.35

87.0

111.0

3303

3503

10

24-09

39.3

1316

4146

995

1148

11.40

1641

120.7

140.5

12.6

.35

95.5

120.0

3676

3880

10

24-10

45.0

1505

4788

1149

1309

13.00

1867

135.1

157.8

14.2

.40

104.0

129.0

4048

4257

10

24-11

50.5

1690

5429

1303

1470

14.60

2093

149.5

175.0

15.7

.45

112.5

138.0

4421

4634

12

24-12

55.3

1852

5983

1436

1610

16.00

2320

164.0

192.3

17.3

.49

121.0

147.0

4794

5011

12

Since 1949, homeowners have depended on us

for quality, value and service.

3633 I Street, P.O. Box 14818
Philadelphia, PA 19134
Phone: (215) 535-8900 Fax: (215) 535-9736
www.crownboiler.com

Commercial Hot Water or Steam Boiler

Commercial Hot Water or Steam Boiler

Beckett Gas Burners

(Natural Gas)

Min. Inlet

Gas

Boiler

Burner

Rate

STD. Motor

Pressure

Train

Model

Model

Control

Voltage

H.P.

(in W.C.)

Size

24-03

CG10.1S

On/Off

120/60/1

1/3

3.2

1”

24-04

CG10.4S

On/Off

120/60/1

1/3

3.6

1”

24-05

CG10.5S

On/Off

120/60/1

1/3

4.3

1-1/4”

24-06

CG10.6S

On/Off

120/60/1

1/3

4.4

1-1/2”

24-07

CG15.3S

Lo/Hi/Lo

120/60/1

1/2

4.0

1-1/2”

24-08

CG15.4S

Lo/Hi/Lo

120/60/1

1/2

4.4

1-1/2”

24-09

CG25.2S

Lo/Hi/Lo

120/60/1

3/4

4.3

1-1/2”

24-10

CG25.3S

Lo/Hi/Lo

120/60/1

3/4

4.9

1-1/2”

24-11

CG25.4S

Lo/Hi/Lo

120/60/1

3/4

4.9

1-1/2”

24-12

CG50.2S

Lo/Hi/Lo

208-240/60/1

2

3.9

1-1/2”

Minimum gas pressures shown are for standard burners only.
See manual for minimum gas pressure when other size gas trains are used.

Beckett Oil Burners

Boiler

Burner

Rate

STD. Motor

Model

Model

Control

Voltage

H.P.

24-03

CF500

On/Off

120/60/1

1/3

24-04

CF800

On/Off

120/60/1

1/3

24-05

CF800

On/Off

120/60/1

1/3

24-06

CF1400

Lo/Hi/Lo

120/60/1

1/2

24-07

CF1400

Lo/Hi/Lo

120/60/1

1/2

24-08

CF1400

Lo/Hi/Lo

120/60/1

1/2

24-09

CF2300A

Lo/Hi/Lo

120/60/1

3/4

24-10

CF2300A

Lo/Hi/Lo

120/60/1

3/4

24-11

CF2500

Lo/Hi/Lo

240/60/1

2

24-12

CF2500

Lo/Hi/Lo

240/60/1

2

S24-12/05 (25M)

PN980521

AVAILABLE FROM

Notes:
1. Trim suffix

S = Steam Boiler

W = Water Boiler

Fuel suffix

N = Natural Gas

O = Oil

2. I=B=R net ratings shown are based on piping and pick-up allowances which vary from 1.333 to 1.289 for steam and 1.15 for water. Consult manufacturer for installations having unusual piping and pick-up

requirements, such as intermittent system operation, extensive piping systems, etc. The I=B=R burner capacity in GPH is based on oil having a heat value of 140,000 BTU per gallon.

3. Firebox volume does not include added volume of 8” extended burner mounting plate (BMP). If 8” BMP is specified (refer to Figure 1), add 0.7 cu. ft. to volume listed above.
4. Boiler ratings are based on 12.5% CO2 (oil) and 9.7% CO2 (natural gas), + .10” (inches) water column pressure at boiler flue outlet. Ratings shown above apply at altitudes up to 1000 feet on oil and 2,000

feet on gas. For altitudes above those indicated, the ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

Maximum Allowable Working Pressure: Steam Boiler – 15 PSI, Water Boiler – 50 PSI

Standard Safety (Relief) Valve Set Pressure: Steam Boiler – 15 PSI, Water Boiler – 30 PSI